Section 4: Operation

Functional Tests and Adjustments

Following transfer switch installation and interconnection,
inspect the entire installation carefully. A competent,
qualified electrician should inspect it. The installation
should comply strictly with all applicable codes,
standards, and regulations. When absolutely certain the
installation is proper and correct, complete a functional
test of the system. 

IMPORTANT: Before proceeding with functional tests,
read and make sure all instructions and information in
this section is understood. Also read the information and
instructions of labels and decals affixed to the switch.
Note any options or accessories that might be installed
and review their operation.

Manual Operation

See 

Figure 4-1

A manual handle is shipped with the

transfer switch and is stored in a bracket (B) within the
cabinet. Manual operation must be checked BEFORE the
transfer switch is operated electrically. To check manual
operation, proceed as follows.

IMPORTANT NOTE: Never manually operate the
transfer switch mechanism while it is energized with
utility or generator power.

1.

Confirm the generator is OFF.

2.

Turn OFF both UTILITY (service disconnect circuit
breaker) and EMERGENCY (generator main line
circuit breaker) power supplies to the transfer
switch.

3.

Note position of transfer mechanism main contacts
by observing the movable contact carrier arm. This
can be viewed through the long narrow slot in the
inside cover of the ATS. The top of the movable
contact carrier arm is yellow to be easily identified.

Manual operation handle in the UP position—LOAD
terminals (T1, T2) are connected to UTILITY
terminals (N1, N2).

Manual operation handle in the DOWN position—
LOAD terminals (T1, T2) are connected to
EMERGENCY terminals (E1, E2).

Close to Utility Source Side

See 

Figure 4-1

. Before proceeding, verify the position of

the switch by observing the position of manual operation
handle. If the handle is UP, the contacts are closed in the
NORMAL (UTILITY) position, no further action is
required. If the handle is DOWN, proceed with Step 1.

1.

With the handle inserted into the movable contact
carrier arm (A), move handle UP. Be sure to hold
on to the handle as it will move quickly after the
center of travel.

2.

Remove manual operating handle from movable
contact carrier arm. Return handle to storage
bracket (B).

Figure 4-1. Manual Operation

(000121)

CAUTION

Equipment damage. Perform functional tests in the 
exact order they are presented in the manual. 
Failure to do so could result in equipment damage.

 

(000132)

DANGER

Electrocution. Do not manually transfer under load. 
Disconnect transfer switch from all power sources 
prior to manual transfer. Failure to do so will result
in death or serious injury, and equipment damage.

(000122)

CAUTION

Equipment damage. Do not use excessive force 
while manually operating the transfer switch. 
Doing so could result in equipment damage.

 

003547

A

B

Summary of Contents for RTG24SHA1

Page 1: ...1 100A RTG42SHA1 200A Register your Generac product at WWW GENERAC COM 888 436 3722 Para espa ol visita http www generac com service support product support lookup SAVE THIS MANUAL FOR FUTURE REFERENC...

Page 2: ...contains or emits chemicals known to the state of California to cause cancer birth defects and other reproductive harm 000004 WARNING California Proposition 65 Engine exhaust and some of its constitue...

Page 3: ...y Source Side 13 Close to Generator Source Side 14 Return to Utility Source Side 14 Voltage Checks 14 Utility Voltage Checks 14 Generator Voltage Checks 14 Generator Tests Under Load 14 Checking Autom...

Page 4: ...Table of Contents iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 5: ...ible circumstance that might involve a hazard The warnings in this manual and on tags and decals affixed to the unit are therefore not all inclusive If using a procedure work method or operating techn...

Page 6: ...connections of the transfer switch Failure to do so will result in death or serious injury 000157 DANGER Electrocution Do not disable or modify the connection box door safety switch Doing so will res...

Page 7: ...ch Failure to do so will result in death or serious injury 000104 DANGER Electrocution Water contact with a power source if not avoided will result in death or serious injury 000188 DANGER Electrocuti...

Page 8: ...Introduction and Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 9: ...standby electric system installations The transfer switch consists of a transfer mechanism utility service disconnect circuit breaker a control relay fuses terminal strip and fuse holder for connecti...

Page 10: ...Code UL 1008 STANDARD FOR SAFETY AUTOMATIC TRANSFER SWITCHES UL 67 Panelboards Marking and Application Guide NOTE It is essential to use the latest version of any standard to ensure correct and curre...

Page 11: ...termined by generator frequency Loads are shed when frequency is less than 58 Hz for three seconds or less than 50 Hz for one half second for 60 Hz systems The SACM can be used in conjunction with ind...

Page 12: ...General Information 8 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 13: ...onvenience and proximity to the utility supply and load center Install the transfer switch as close as possible to the electrical loads that are to be connected to it Mount the switch vertically to a...

Page 14: ...NEC Article 210 4 Connecting Power Source and Generator Power Supply Installation and interconnection diagrams are provided in this manual NOTE All installations must comply with national state and l...

Page 15: ...wiring connection details Recommended wire gauge sizes for this wiring depends on the length of the wire as recommended in the following chart Exception Conductors of AC and DC circuits rated 1000 vol...

Page 16: ...is in utility mode The contacts will open when the transfer switch is in the standby power mode Figure 3 5 Auxiliary Contact NOTE Auxiliary Contact is rated 10 amps at 125 or 250 volts AC and 0 6 amp...

Page 17: ...sm main contacts by observing the movable contact carrier arm This can be viewed through the long narrow slot in the inside cover of the ATS The top of the movable contact carrier arm is yellow to be...

Page 18: ...nsfer switch ratings turn OFF the generator supply to the transfer switch 6 On the generator panel select the OFF mode to shut down the generator NOTE Do NOT proceed until generator AC output voltage...

Page 19: ...utility power source Approximately one minute after re transfer the engine should shut down With the generator in the AUTOMATIC mode the system is now set for fully automatic operation Installation S...

Page 20: ...Operation 16 Automatic Transfer Switch Owner s Manual Testing The Smart Management Module Refer to the SMM Owner s Installation Manual for testing that product...

Page 21: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 17 Section 5 Drawings and Diagrams Installation Drawings Installation Drawing No 10000005900 100A 2 of 2...

Page 22: ...Drawings and Diagrams 18 Automatic Transfer Switch Owner s Manual Installation Drawing No 10000005900 200A 1 of 2...

Page 23: ...Transfer Switch Owner s Manual 19 Interconnection Drawings Interconnection Drawing 10000005901 Air Cooled 100A Generator page 1 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG24SHA1 DRAWING 1000...

Page 24: ...s 20 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005901 Air Cooled 100A Generator page 2 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG24SHA1 DRAWING 10000005901 REVIS...

Page 25: ...s Automatic Transfer Switch Owner s Manual 21 Interconnection Drawing 10000005901 Air Cooled 200A Generator page 1 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG42SHA1 DRAWING 10000005901 REVIS...

Page 26: ...ms 22 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005901 Air Cooled 200A Generator page 2 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG42SHA1 DRAWING 10000005901 REVI...

Page 27: ...utomatic Transfer Switch Owner s Manual 23 Interconnection Drawing 10000005855 Liquid Cooled 100A Generator page 1 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG24SHA1 DRAWING 10000005855 RE...

Page 28: ...4 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005855 Liquid Cooled 100A Generator page 2 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG24SHA1 DRAWING 10000005855 RE...

Page 29: ...utomatic Transfer Switch Owner s Manual 25 Interconnection Drawing 10000005855 Liquid Cooled 200A Generator page 1 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG42SHA1 DRAWING 10000005855 RE...

Page 30: ...6 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005855 Liquid Cooled 200A Generator page 2 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG42SHA1 DRAWING 10000005855 RE...

Page 31: ......

Page 32: ...rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W2929...

Reviews: