Section 5: Fuel Conversion/Gas Connections
Installation Guidelines For 60 Hz Air-cooled Generators
19
Natural Gas Pipe Sizing
To determine correct gas pipe size, find the kW rating of
the generator in the left column, and trace to the right.
The number to the right is the maximum length
(measured in meters/feet) allowed for the pipe sizes on
top. Pipe sizes are measured by inside diameter (ID) to
include any fittings, valves (must be full flow), elbows,
tees or angles.
NOTE:
Add 2.5 ft (0.76 m) per any bend, tee or angle in
the pipe to the overall distance. Tables based on
schedule 40 black pipe.
LP Vapor Pipe Sizing
To determine correct LP Vapor pipe size, find the kW
rating of the generator in the left column, and trace to the
right. The number to the right is the maximum length
(measured in meters/feet) allowed for the pipe sizes on
top. The pipe sizes are measured by inside diameter (ID)
to include any fittings, valves (must be full flow), elbows,
tees or angles. Add 2.5 feet (0.76m) per any bend, tee or
angle in the pipe to the overall distance.
NOTE:
Pipe sizes are using a second stage regulator.
NOTE:
The minimum LP tank size is 250 gallons (946 L),
unless unit calculations dictate use of a larger tank.
Vertical tanks, which are measured in pounds (or
kilograms), will not usually meet the minimum tank size
requirement. A 1050 lb (476 kg) vertical tank size
minimum is required.
Installing and Connecting Gas Lines
Natural gas and LP vapor are highly volatile substances.
Strict adherence to all safety procedures, codes,
standards and regulations is essential.
Gas line connections should be made by a certified
plumber familiar with local codes. Always use AGA-
approved gas pipe and a quality pipe sealant or joint
compound.
Table 5-1. Natural Gas Pipe Sizing
For 5-7 inches of water column
(9-13 mm mercury)
For 3.5-5 inches of water column
(7-9 mm mercury)
Allowable Pipe Distances (feet / meters)
Pipe Size
(in / mm)
0.75 / 19
1 / 25
1.25 / 32
1.5 / 38
2 / 51
1 / 25
1.25 / 32
1.5 / 38
8 kW
55 / 16.76
200 / 60.96
820 / 249.94
—
—
20 / 6.1
60 / 18.29
175 / 53.34
11 kW
20 / 6.1
85 / 25.91
370 / 112.78
800 / 243.84
—
—
60 / 18.29
175 / 53.34
16-22 kW
—
20 / 6.1
130 / 39.62
305 / 92.96
945 / 288.04
10 / 3.05
60 / 18.29
125 / 38.1
Table 5-2. LP Vapor Pipe Sizing
For 10-12 inches of water column (19-22 mm mercury)
Allowable Pipe Distances (feet / meters)
Pipe Size (in / mm)
0.75 / 19
1 / 25
1.25 / 32
8 kW
165 / 50.29
570 / 173.74
—
11 kW
70 / 21.33
255 / 77.72
1000 / 304.8
16 kW
25 / 7.62
130 / 39.62
540 / 164.59
22 kW
15 / 4.57
115 / 35.05
480 / 146.3
(000192)
DANGER
Summary of Contents for rtg10eza1
Page 47: ......
Page 52: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank ...
Page 64: ...Operation 12 Automatic Transfer Switch Owner s Manual This page intentionally left blank ...
Page 70: ...Drawings and Diagrams 18 Automatic Transfer Switch Owner s Manual ...
Page 71: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......