Generac Power Systems PWRview RXEMW200A3 Owner'S Manual Download Page 21

Operation

Automatic Transfer Switch Owner’s Manual

17

5.

Set the generator main circuit breaker to ON or
CLOSED. The generator now powers all LOAD
circuits. Check generator operation under load as
follows:

Turn on electrical loads to the full rated watt-
age/amperage capacity of the generator. DO
NOT OVERLOAD.

With maximum rated load applied, check volt-
age and frequency across transfer switch ter-
minals E1 and E2. Voltage should be greater
than 230 VAC (240 VAC system); frequency
should be greater than 59 Hz.

Verify the gas pressure remains within accept-
able parameters (see the generator Installation
manual).

Let the generator run under rated load for at
least 30 minutes. With unit running, watch for
unusual noises, vibration, or overheating that
might indicate a problem.

6.

When checkout under load is complete, set main
circuit breaker of the generator to OFF or OPEN.

7.

Let the generator run at no-load for several minutes.
Then, shut down by selecting the OFF.

8.

Move the main switch contacts back to the utility
position. 

NOTE: 

See 

Manual Operation

. Handle and operating

lever of transfer switch should be in down position.

9.

Set the utility service disconnect circuit breaker of
the transfer switch to ON or CLOSED.

10.

The system is now set for fully automatic operation.

Checking Automatic Operation

To check the system for proper automatic operation,
proceed as follows:

1.

Verify generator is OFF.

2.

Set the utility service disconnect circuit breaker of
the transfer switch to OFF or OPEN.

3.

Verify switch is de-energized.

4.

Install front cover of the transfer switch.

5.

Set the utility service disconnect circuit breaker of
the transfer switch to ON or CLOSED.

6.

Set the generator main circuit breaker to ON.

7.

On the generator panel, select AUTO. The system
is now ready for automatic operation.

8.

Set the utility service disconnect circuit breaker of
the transfer switch to OFF or OPEN.

With the generator ready for automatic operation, the
engine should crank and start when the utility source
power is turned OFF after a five second delay (factory
default setting). After starting, the transfer switch should
connect load circuits to the standby side after a five (5)
second warm-up delay. Let the system operate through

its entire automatic sequence of operation.

NOTE: 

Timer durations may differ between generators

and settings.

With the generator running and loads powered by
generator AC output, set the utility service disconnect
circuit breaker of the transfer switch to ON or CLOSED.
The following should occur:

After approximately 15 seconds, the switch should
transfer loads back to the utility power source.

Approximately one minute after re-transfer, the
generator should shut down.

With the generator in AUTOMATIC, the system is now
set for fully automatic operation.

Installation Summary

1.

Verify the installation has been properly performed
as outlined by the manufacturer and that it meets
all applicable laws and codes.

2.

Verify proper operation of the system as outlined in
the appropriate installation and owner’s manuals.

3.

Educate the end-user on the proper operation,
maintenance and service call procedures.

NOTE: 

The Utility Power Circuit Breaker in the transfer

switch must be turned OFF to simulate a utility outage.
Shutting off the main disconnect in a subpanel connected
to the transfer switch will NOT simulate an outage. 

Shutting Generator Down While 

Under Load or During a Utility Outage

IMPORTANT NOTE: To avoid equipment damage,
follow these steps, in order, during utility outages.
Shutdowns may be required during utility outages to
perform routine maintenance or to conserve fuel.
To turn generator OFF:

1.

Set utility MLCB to OFF (OPEN).

2.

Set generator MLCB (generator disconnect) to
OFF (OPEN).

3.

Allow generator to run for cool-down for approxi-
mately one minute.

4.

Set generator to OFF at the controller.

5.

Remove 7.5A fuse from controller.

To turn generator back ON:

1.

Install 7.5A fuse in controller.

2.

Verify generator MLCB (generator disconnect) is
OFF (OPEN).

Automatic start-up. Disconnect utility power and 
render unit inoperable before working on unit. 
Failure to do so will result in death or serious injury.

(000191)

DANGER

Summary of Contents for PWRview RXEMW200A3

Page 1: ...Entrance Model Number RXEMW200A3 SERIAL NUMBER _________________________ DATE PURCHASED ________________________ WWW GENERAC COM 888 436 3722 Para espa ol visita http www generac com service support...

Page 2: ...ii Automatic Transfer Switch Owner s Manual 000393a WARNING CANCER AND REPRODUCTIVE HARM www P65Warnings ca gov...

Page 3: ...r Conditioner Load 11 Auxiliary Contact 13 Fault Current Label 13 Installing PWRview Antenna 14 Connecting PWRview CTs 14 Section 4 Operation Functional Tests and Adjustments 15 Manual Operation 15 Cl...

Page 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 5: ...lusive If using a procedure work method or operating technique that the manufacturer does not spe cifically recommend verify that it is safe for others and does not render the equipment unsafe Through...

Page 6: ...the transfer switch Failure to do so will result in death or serious injury 000157 DANGER Electrocution Do not disable or modify the connection box door safety switch Doing so will result in death or...

Page 7: ...efore working on utility connections of the transfer switch Failure to do so will result in death or serious injury 000104 DANGER Electrocution Water contact with a power source if not avoided will re...

Page 8: ...Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 9: ...inal lugs are standard The conductor size range is as follows This transfer switch is suitable for control of motors electric discharge lamps tungsten filament and electric heating equipment where the...

Page 10: ...following NFPA 70 National Electrical Code UL 1008 Standard for Safety Automatic Transfer Switches NOTE It is essential to use the latest version of any standard to guarantee correct and current infor...

Page 11: ...the top priorities then up to four SMMs as Priorities 5 8 Use only select A C priorities on the SACM as the top priorities then use additional SMMs as the remaining priorities A SMM can share a priori...

Page 12: ...General Information 8 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 13: ...l the transfer switch as close as possible to the electrical loads that are to be connected to it Mount the switch vertically to a rigid supporting structure To prevent switch distortion level all mou...

Page 14: ...to handle the maximum current to which they will be subjected based on the 75 C column of tables charts etc used to size conductors The installation must comply fully with all applicable codes standar...

Page 15: ...ductor within the equipment cable or conduit See NEC 300 3 C 1 Connecting SACM See Figure 3 3 The SACM can control an air conditioner 24 VAC directly Control of Air Conditioner Load 1 Route the thermo...

Page 16: ...nditioner 2 E Thermostat 3 F Air Conditioner 3 G Thermostat 4 H Air Conditioner 4 I Spare Fuse Holder T1 fused Battery Charge N1 fused Utility Sense N2 fused Utility Sense 0 DC Ground 194 12 VDC 23 Tr...

Page 17: ...ining the unit Owner s Manual and transfer switch manual operating handle The 2017 NEC requires that the short circuit current rating of the transfer equipment based on the type of overcurrent protect...

Page 18: ...firmly to ensure a good seal 4 Insert antenna cable from PWRview monitor into the antenna carrier 5 Screw the included weatherproof antenna E onto the antenna cable until it is snug against the antenn...

Page 19: ...an be viewed through the long narrow slot in the inside cover The top of the movable contact carrier arm is yellow to be easily identified Manual operation handle in the UP position LOAD terminals T1...

Page 20: ...it breaker CB1 to ON or CLOSED 4 With an accurate AC voltmeter and frequency meter check the no load voltage and frequency Measure across ATS terminal lugs E1 to E2 E1 to NEUTRAL and E2 to NEUTRAL 5 W...

Page 21: ...when the utility source power is turned OFF after a five second delay factory default setting After starting the transfer switch should connect load circuits to the standby side after a five 5 second...

Page 22: ...sabled 5 After five 5 minutes verify A C 1 is energized and Status LED A C 1 is ON 6 After another 15 seconds verify A C 2 is energized and Status LED A C 2 is ON 7 After another 15 seconds verify Loa...

Page 23: ...tartup procedure and connect to the Wi Fi network 3 Verify the PWRview monitor has establlished communication with the Wi Fi network through the PWRview Installer app on your smartphone Figure 4 3 PWR...

Page 24: ...Operation 20 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 25: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 21 Section 5 Drawings and Diagrams Installation Drawings No 10000012171 150 200A SE...

Page 26: ...TRANSFER 194 12V 0 GROUND N2 N1 T1 2 1 2 1 2 A C 4 A C 3 N2 N1 TRANSFER SWITCH SERVICE RATED ENTRANCE UTILITY SUPPLY FROM SERVICE DISCONNECT N1 N2 E1 T2 T1 E2 SERVICE ENTRANCE SWITCH INTERCONNECT NOT...

Page 27: ...C 4 A C 3 A C 2 A C 1 N2 N1 T1 194 23 N1 N2 T1 0 23 TRANSFER 194 12V 0 GROUND N2 N1 T1 2 1 2 1 2 A C 4 A C 3 N2 N1 TRANSFER SWITCH SERVICE RATED ENTRANCE UTILITY SUPPLY FROM SERVICE DISCONNECT N1 N2...

Page 28: ...Drawings and Diagrams 24 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 29: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 25 This page intentionally left blank...

Page 30: ...Drawings and Diagrams 26 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 31: ......

Page 32: ...rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W2929...

Reviews: