MMG120 Generac Specifications Continued:  

Manufactured by Magnum Power Products LLC., a wholly owned subsidiary of Generac Power Systems, Inc.                                                                                                 

                                                                                    Phone: 800-926-9768  Fax: 920-361-2214  www.m-p-llc.com  

 

Page 2 of 4 

4/12

 

o

 

Six LED indicators w/ lamp test 

 

Alarm / Fault (Red)  

 

Ready / Manual (Red) 

 

Running (Green) 

 

Warning (Yellow) 

 

Ready / Auto (Green) 

 

Supplying Load (Green) 

 

Push buttons for easy operation 

o

 

Manual or Auto Start 

o

 

Engine Start or Stop 

o

 

Alarm Cancel & Fault Reset 

o

 

Scrolling Arrows for Diagnostic Information 

 

System kW output display 

 

Line output & frequency display 

 

Engine diagnostic display 

 

Oil pressure 

 

Engine temperature 

 

Fuel level 

 

Battery 

 

System hours 

 

Running hours 

 

kW hours 

 

Time to service 

o

 

Alarm list – warnings / shutdowns are date & time stamped 

 

Fuel level: warning – 15%; shutdown – 5%  

 

Overspeed protection: shutdown – 115% 

 

Oil pressure: warning – 25 psi; shutdown – 20 psi 

 

Coolant temperature: warning – 220°F; shutdown – 230°F 

 

Battery voltage: over – 15VDC; under – 11VDC 

 

Generator over voltage: warning – 110%; shutdown – 111% 

 

Generator under voltage: warning – 87%; shutdown – 86% 

 

Generator over frequency: warning – 105%; shutdown – 110% 

 

Generator under frequency: warning – 95%; shutdown – 90% 

 

Over current shutdown

 

ELECTRICAL CONTROLS 

 

Remote start / stop contacts located next to lug box 

 

Lockable control box door with diagnostics window 

 

Lockable lug box with safety switch 

o

 

Trips main breaker when lug door is opened 

o

 

Disables voltage regulator 

 

Cable entry guides to the lug box 

o

 

Restricts access of foreign objects 

 

Output ground connection lug inside lug box 

 

Convenience receptacles with individual breakers (restricted use in high wye mode) 

o

 

(2) 120V 20 Amp GFCI duplex outlets (Nema 5-20R type) 

o

 

(3) 125 / 250V 50 Amp, 3 pole, 4 wire twistlock (Non-Nema 6369) 

 

Panel mounted rheostat for voltage adjustment - +/- 10% 

 

1000 CCA wet cell battery 

 

Summary of Contents for MMG120

Page 1: ... Radiator and oil drains plumbed to exterior Rubber vibration dampers isolate engine generator from frame Disposable air filter paper element Air filter restriction indicator mounted on control panel 60 Hz engine generator Electronic isochronous governing GENERATOR Marathon Electric o Brushless o 4 pole o Class H insulation Voltage regulation 1 with Marathon SE350 Voltage Regulator SYSTEM OUTPUT 3...

Page 2: ...tion shutdown 115 Oil pressure warning 25 psi shutdown 20 psi Coolant temperature warning 220 F shutdown 230 F Battery voltage over 15VDC under 11VDC Generator over voltage warning 110 shutdown 111 Generator under voltage warning 87 shutdown 86 Generator over frequency warning 105 shutdown 110 Generator under frequency warning 95 shutdown 90 Over current shutdown ELECTRICAL CONTROLS Remote start s...

Page 3: ...ifting point Multi lingual operating safety decals Document holder with operating manual including AC DC wiring diagrams TRAILER DOT approved tail side brake and directional lights o Recessed rear lights Transportation tie downs Safety chains with spring loaded safety hooks 3 lunette ring hitch 2 6000 lb axles with surge brakes 5000 lb tongue jack with footplate 7 50x16E 6 W tubeless tires 10 ply ...

Page 4: ...ion phase switch Single phase 120 240V Zig Zag Three phase 120 208V Low Wye Three phase 277 480V High Wye Three phase 120 240V Delta Dedicated voltage configurations Buck Transformer kit Provides 120V at GFCI outlets when in 277 480V Cam locks SYSTEM CONTROLS OPTIONS Auxiliary strobe audible indication for soft hard alarm conditions COOLANT OPTIONS 60 40 Coolant cold weather applications ENCLOSURE...

Reviews: