28
Owner’s Manual for Mobile Generator
Operation
Using a Booster Battery or
Charger (if equipped)
See
. A 12 volt booster battery can be
connected in parallel with batteries on the unit to aid in
cold weather starting. ALWAYS use heavy-duty jumper
cables.
Parallel:
•
Amps = Twice as a single battery
•
Volts = Same as single battery
Figure 3-3. Parallel
1. Connect booster battery or batteries to produce the
required system current.
NOTE:
To avoid sparks, do not allow the free ends of
jumper cables to touch engine.
2. Connect one end of jumper cable to the POSITIVE
(+) post of the booster battery.
3. Connect the other end of the jumper cable to the
POSITIVE (+) post of battery connected to starter.
4. Connect one end of the other jumper cable to the
NEGATIVE (-) post of the booster battery.
5. Complete the hookup by making the last
connection of the NEGATIVE (-) cable to a good
ground on the engine frame and away from the
batteries.
6. Start the engine. Disconnect jumper cables
immediately after engine starts. Always disconnect
NEGATIVE (-) cable first.
Generator Output Connections
The installation should be in compliance with the national
electrical code (NEC), state, and local regulations.
See
. The unit is equipped with connection
lugs (A), located on the lower portion of the control box
behind the lug box door. The lugs provide connection
points to attach external loads to the generator. A large
decal on the inside of the connection lug door details the
proper connections for selected voltages.
Connections to the lugs should be made by running the
power cables up through the opening in the bottom of the
box.
IMPORTANT NOTE: Do not make any connections
directly to the lugs without routing the cables
through the opening. Use a hex-wrench to tighten the
cable connections.
(000137a)
WARNING
Explosion. Batteries emit explosive gases while
charging. Keep fire and spark away. Wear protective
gear when working with batteries. Failure to do so
could result in death or serious injury.
(000138a)
WARNING
Risk of burns. Batteries contain sulfuric acid and can
cause severe chemical burns. Wear protective gear
when working with batteries. Failure to do so could
result in death or serious injury.
(000167a)
Equipment damage. Do not make battery
connections in reverse. Doing so will result
in equipment damage.
CAUTION
004508
(000237)
DANGER
Electrical backfeed. Use only approved switchgear to
isolate generator from the normal power source.
Failure to do so will result in death, serious injury,
and equipment damage.
(000157)
DANGER
Electrocution. Do not disable or modify the
connection box door safety switch. Doing so
will result in death or serious injury.
(000156)
DANGER
Electrocution. Before connections are made to
the unit, verify the main circuit breaker and
battery disconnect switch are OFF. Failure to do
so will result in death or serious injury.
(000155a)
WARNING
Electric shock. Only a trained and licensed electrician
should perform wiring and connections to unit. Failure to
follow proper installation requirements could result in death,
serious injury, and equipment or property damage.
Summary of Contents for MDG25IF4
Page 40: ...36 Owner s Manual for Mobile Generator Operation This page intentionally left blank...
Page 46: ...42 Owner s Manual for Mobile Generator Troubleshooting This page intentionally left blank...
Page 57: ...Owner s Manual for Mobile Generator 53 Wiring Diagrams This page intentionally left blank...
Page 58: ...54 Owner s Manual for Mobile Generator Wiring Diagrams This page intentionally left blank...
Page 59: ......