Operation
18
Owner’s Manual for MLT Light Tower
MDC List of Alarms
No.
Events
Specification
Protection
Type
Information on
Binary Output
Available
Description
1
AnInIOM Sd
SD
YES
Shutdown alarm configurable on the input of IG-IOM/IGS-
PTM.
2
AnInIOM Wrn
WRN
YES
Warning alarm configurable on the input of IG-IOM/IGS-PTM.
3
Battery Flat (low
battery)
SD
YES
If the controller switches off during starting sequence due to
bad battery condition, it doesn’t try to start again and acti-
vates this protection.
4
Binary Input
CONFIG.
YES
Configurable Warning/Shutdown alarms on the inputs of IL-
NT.
5
ChrgAlternFail
WRN
YES
Failure of the alternator to charge the battery.
6
EmergencyStop
SD
NO
If the red emergency stop switch is pushed or opened, shut-
down is immediately activated.
7
Engine Temp Sd
SD
NO
Water temperature is greater than
Sd Water Temp
setpoint.
8
Engine Temp Wrn
WRN
YES
Water temperature is greater than
Wrn Water Temp
setpoint.
9
Fgen<, >
SD
YES
The generator frequency is out of limits given by
Gen >f
and
Gen <f
setpoints.
10
Fuel Level Sd
SD
YES
Fuel level is smaller than
Sd Fuel Level
setpoint (5%). (Not
available on MLG, MLT or MTT units.)
11
Fuel Level Wrn
WRN
YES
Fuel level is smaller than
Wrn Fuel Level
setpoint (15%). (Not
available on MLG, MLT or MTT units.)
12
GCB fail
SD
NO
Failure of the generator circuit breaker.
13
Igen unbl
SD
NO
The generator current is unbalanced.
14
Low BackupBatt
WRN
NO
RTC backup battery is flat (low).
15
Oil Press Sd
SD
NO
Oil pressure is smaller than
Sd Oil Press
setpoint.
16
Oil Press Wrn
WRN
YES
Oil pressure is smaller than
Wrn Oil Press
setpoint.
17
Overload
SD
YES
The load is greater than the value given by
Overload
setpoint.
18
Overspeed
SD
YES
The protection comes active if the speed is greater than
Overspeed
setpoint.
19
ParamFail
NONE
NO
Wrong checksum of parameters. Happens typically after
downloading new firmware or changing of the parameter. The
controller stays in INIT mode. Check all parameters, write at
least one new parameter.
20
PickupFault
SD
NO
Failure of the magnetic pick up sensor for speed measure-
ment.
21
Sd IOM fail
SD
NO
Shutdown alarm in case of lost connection to IOM/IGS-PTM
module.
22
SprinkIActive
WRN
NO
The protection is active if the output
Sprinkler
is closed.
23
Start failed
SD
YES
Unit did not start.
24
Stop fail
SD
YES
Unit did not stop.
25
Vbat
WRN
YES
Battery voltage is out of limits given by
Batt Undervolt
set-
points.
26
Underspeed
SD
YES
During starting of the engine, when the RPM reaches the
value of
Starting RPM
setpoint, the starter is switched off and
the speed of the engine can drop under
Start RPM
again.
Then the
Underspeed
protection becomes active. Protection
evaluation starts 5 seconds after startup.
27
Vgen<, >
SD
YES
The generator voltage is out of limits given by
Gen <V
and
Gen <V
setpoints.