background image

6

Generac

®

Power Systems, Inc.

1.10 VOLTAGE REGULATOR

ADJUSTMENT

With the frequency between 61-62 Hertz, slowly turn
the slotted potentiometer (Figure 1.4) until line volt-
age reads 244-252 volts.

NOTE:

You must remove the roof to adjust the voltage
regulator.

Figure 1.4 – Voltage Adjustment Potentiometer

NOTE:

The voltage regulator is housed in the generator's
control

panel.

The

regulator

maintains

a voltage in direct proportion to frequency at a 2-
to-1 ratio. For example, at 62 Hertz, line-to-neu-
tral voltage will be 124 volts.

1.11 ADDITIONAL GENERATOR

FEATURES

1.11.1 8 KW AND 10 KW UNITS

The 8 kW and 10 kW air-cooled Guardians offer addi-
tional features that are not factory preset:

1.

Remote Start – This allows for remote starting of
the generator by means of the #183 (common)
and

#178

(normally

open)

lines

with

the

Auto/Off/Manual switch set to AUTO. Closure of
the circuit starts the unit; opening of the circuit
stops the unit. See Figure 1.5.

NOTE:

This function will work only with the unit in the
AUTO mode.

Figure 1.5 – Remote Start/Alarm Options

–Type 14 AWG wire is recommended.

–These options should be wired to the unit by a qualified electrician or
Generac/Guardian Authorized Dealer.

2.

Remote/Common Alarm – This allows for an
alarm, light, horn, etc., to activate when any fault
has occurred. Lines #210 (common) and #211
(normally open) provide a “closure” on common
fault, which can be used for 120 volts, 10 amps
maximum. See Figure 1.5.

3.

Remote Not Auto – The generator will not auto-
matically start during a utility failure.

Section 1 — Post Installation Start-up and Adjustments

Guardian Air-cooled Generators

Summary of Contents for GUARDIAN 04079-2

Page 1: ...POWER SYSTEMS INC Post Installation Start up and Adjustment Manual Air cooled Prepackaged Standby Generators Models 04109 2 8 kW 04079 2 10 kW...

Page 2: ...n properly purged and leak tested in accordance with applicable fuel gas codes All fuel shutoff valves in the fuel supply lines must be open Never operate the engine with the oil level below the Add m...

Page 3: ...main circuit breaker to its OFF or open position Initial tests will be con ducted at no load condition 6 On the generator panel set the Auto Off Manual switch to MANUAL The engine should crank and st...

Page 4: ...s connected to the util ity power source side 3 Turn ON the utility power supply to the transfer switch using the means provided such as a util ity main line circuit breaker 4 Set the Auto Off Manual...

Page 5: ...olt Figure 1 3 2 Push the spring end of the governor lever clock wise to the wide open throttle position of the lever Hold the governor lever at wide open throttle and with a screwdriver rotate the go...

Page 6: ...This allows for remote starting of the generator by means of the 183 common and 178 normally open lines with the Auto Off Manual switch set to AUTO Closure of the circuit starts the unit opening of t...

Page 7: ...Generac Power Systems Inc 7 Section 2 Notes Guardian Air cooled Generators...

Page 8: ...Part No D1962 GENERAC POWER SYSTEMS INC 757 NORTH NEWCOMB ROAD WHITEWATER WI 53190 PH 262 473 5514 FAX 262 472 6511 Revision 0 11 08 00 Printed in U S A...

Reviews: