FUEL HOOKUP AND CHECK FOR LEAKS
21a.
Make the connection between the rigid fuel piping
and the generator using the supplied threaded flexible
fuel line. Use a pipe sealant suitable for gaseous fuel
connections. Check connections for leaks by opening
manual fuel shut-off valve and swab, or spray, con-
nections with soapy water. If a leak exists, the area will
bubble with the presence of the soapy water.
21b.
If a leak is located, shut off fuel and disconnect flex-
ible piping. Dry the threaded ends and reapply an
adequate amount of pipe sealant. Reconnect flexible
fuel line, open fuel supply and recheck for leaks. If
leak still exists, repeat step 21b.
22.
Follow all generator installation and setup instructions
in the Installation and Owner’s Manual provided with
the generator. During testing performed in Section 2 of
the generator Installation and Owner’s Manual, utility
power supply to the Automatic Transfer Switch/Load
Center can be controlled using the 40 or 70 amp feeder
circuit breaker located in the main distribution panel.
One (1) Foot Flexible
Fuel Line
21
19
Grounding
Lug
Residential Transfer Switch Installation Guide
Summary of Contents for G0058821
Page 10: ...8 Installation Drawing 0H6393 A ...
Page 11: ...9 Installation Drawing 0H6393 A ...
Page 12: ...10 10 Installation Drawing 0H6392 C ...
Page 13: ...11 Electrical Schematic Drawing 0H6386 B ...
Page 14: ...12 Wiring Diagram Drawing 0H6385 A ...
Page 15: ...13 Wiring Diagram Drawing 0H6385 A ...
Page 16: ...Part No 0H6391 Revision F 09 26 12 Catalog No KGATX0316100 1SI Printed in U S A ...
Page 18: ...16 ...
Page 26: ...Parte No 0H6391 Revisión F 26 09 12 Catálogo No KGATX0316100 1SI Impreso en los EE UU ...
Page 28: ...26 26 26 ...
Page 36: ...Référence 0H6391 Révision F 26 09 12 Catalogue n KGATX0316100 1SI Imprimé aux États Unis ...