Generac Power Systems CENTURION SERIES Specification Download Page 3

3 of 5

**Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters. Rating definitions - Standby: Applicable 

for supplying emergency power for the duration of the utility power outage.  No overload capability is available for this rating.  (All ratings in accordance with BS5514, ISO3046 and DIN6271).  * Maximum 
wattage and current are subject to and limited by such factors as fuel Btu/megajoule content, ambient temperature, altitude, engine power and condition, etc.  Maximum power decreases about 3.5 percent for 
each 1,000 feet (304.8 meters) above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60°F).

Generator

Model

005888-0

Rated Maximum Continuous Power Capacity (LP)

7,000 Watts* 

Rated Maximum Continuous Power Capacity (NG) 

6,000 Watts*

Rated Voltage

240 

Rated Maximum Continuous Load Current – 240 Volts

29.2 / 25

Main Line Circuit Breaker

30 Amp

Phase

1  

Number of Rotor Poles

Rated AC Frequency

60Hz

Power Factor

1.0

Battery Requirement (not included) 

Group 26R, 12 Volts and 525 CCA Minimum

Unit Weight (Pounds/Kilos)

250/113.4

Dimensions (L x W x H) in./mm

24.4 x 30.2 x 33/618.5 x 767.5 x 837

Sound output in dB(A) at 23 ft. (7m) with generator operating at normal load**

67

Engine

Type of Engine

GENERAC OHV

Number of Cylinders

1

Displacement

432cc

Cylinder Block

Aluminum w/Cast Iron Sleeve

Valve Arrangement

Overhead Valve

Ignition System

Solid-state w/Magneto

Governor System

Mechanical

Starter

12 VDC

Oil Capacity Including Filter

Approx. 1.1 Qts./1.0L

Operating RPM

3,600

Fuel Consumption
Natural Gas 

 

ft³/hr (m³/hr)

 

1/2 Load

 

Full Load

Liquid Propane

 

ft

3/hr (gal/hr) [Liters/hr]

 

1/2 Load

 

Full Load

85 (2.41)

148 (4.19)

36 (0.99) [3.75]
46 (1.26) [4.79]

Note: 

Fuel pipe must be sized for full load. 

Required fuel pressure to generator fuel inlet at all load ranges - 5-7" water column (9-13mm mercury) for natural gas, 10-12" water column (19-22mm 

mercury) for LP gas. 

For Btu content, multiply ft

3/hr x 2500 (LP) or ft3/hr x 1000 (NG)

For Megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG)

Controls

Digital LED Indicators

Simple user interface for ease of operation.

Mode Switch: 

Auto 

Automatic Start on Utility failure. 7 day exerciser.

 Off

Stops unit. Power is removed. Control and charger still operate.

 

Manual/Test (start)

Start with starter control, unit stays on. If utility fails, transfer to load takes place.

Engine Start Sequence

Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration)

Engine Warm-up

5 sec.

Engine Cool-Down

1 min.

Starter Lock-out

Starter cannot re-engage until 5 sec. after engine has stopped.

2.5  Amp Timed Trickle Battery Charger

Standard

Automatic Voltage Regulator w/Overvoltage Protection

Standard

Automatic Low Oil Pressure Shutdown

Standard

Overspeed Shutdown

Standard, 72Hz

High Temperature Shutdown

Standard

Overcrank Protection

Standard

Safety Fused

Standard

ES Standby Generator System - 7 kW

 specifications

7kW