Dual Utility Transfer Switch
Source 1 is available
Close Source 1
(Energize K1)
Source 1 is powering the load
Source 1 becomes unavailable
(or Go To Emergency)
Is Source 2
Available?
TDNE timer times out
Open Source 1
(Energize K2)
Close Source 2
(Energize K2)
Source 2 is powering the load
Is Source 1
Available?
TDEN timer times out
Yes
No
No
Yes
Open Source 2
(Energize K1)
Close Source 1
(Energize K1)
Source 1 is powering the load
Sends pretransfer signal
TPRE timer times out
(If Source 1 is Available)
Sends pretransfer signal
TPRE timer times out
IB01602078E
For more information visit: www.generac.com