Generac Power Systems 20 kW LP Owner'S Manual Download Page 30

Maintenance

28

Owner’s Manual for 60 Hz Air-Cooled Generators

Figure 4-8. Valve Clearance Adjustment (11-22 kW)

6.

Turn the pivot ball stud (D) using a 14 mm wrench
(9 kW units), 8 mm wrench (11 kW units), or 10 mm
Allen wrench (16-22 kW units) while checking
clearance between the rocker arm (E) and the
valve stem (F) with a feeler gauge. Adjust
clearance as per 

Specifications

NOTE: 

Hold the rocker arm jam nut in place as the pivot

ball stud is turned.

7.

When valve clearance is correct, hold the pivot ball
stud (B) in place with a wrench and tighten the
rocker arm jam nut. Tighten the jam nut according
to the following torque specifications:

8.

After tightening the jam nut, recheck valve
clearance to verify it did not change.

9.

Install new valve cover gasket.

10.

Install the valve cover. Tighten fasteners in a cross
pattern, torquing to:

NOTE: 

 Start all four screws before tightening, or it will

not be possible to get all the screws in place. Verify the
valve cover gasket is in place.

11.

Install spark plugs and torque to 18 ft-lbs (25 Nm).

12.

Reattach the spark plug wire to the spark plug.

13.

Repeat the process for the other cylinder if
necessary.

Battery Maintenance

The battery should be regularly inspected per the

Service Schedule

. Contact an IASD for assistance if

necessary.
Proceed as follows to inspect the battery:

1.

Press the OFF button to shut down the generator,
then lift the lid and remove the front panel.

2.

Remove the 7.5 amp fuse from the control panel.

3.

Remove the intake side panel. (See 

Intake Side

Panel Removal

.)

4.

See 

Figure 4-1

. Disconnect the white battery

charger cable.

5.

See 

Figure 4-9

. Inspect the battery posts and

cables for tightness and corrosion. Tighten and
clean as necessary.

Figure 4-9. Battery Cables

6.

(Unsealed batteries only): Completely disconnect
the battery. Check the battery fluid level and, if
necessary, fill with distilled water only. DO NOT
use tap water. Also, have an IASD or a qualified
service technician check the state of charge and
condition.

7.

When inspection is complete, reconnect the battery
cables, the battery charger cable, reinstall the
intake side panel, and reinstall the 7.5 amp fuse.

8.

Reinstall the front panel and close the generator lid.

9.

Place the controller in AUTO mode.

9 kW

53 in-lbs (6.0 Nm)

11 kW

72 in-lbs (8.2 Nm)

16–22kW

174 in-lbs (19.68 Nm)

9 kW

80 in-lbs (9.0 Nm)

11–22kW

60 in-lbs (6.8 Nm)

002380

C

D

E

F

001832

+

(000162)

WARNING

Explosion. Do not dispose of batteries in a fire. 
Batteries are explosive. Electrolyte solution can cause

burns and blindness. If electrolyte contacts skin or eyes, 
flush with water and seek immediate medical attention.

(000137a)

WARNING

Summary of Contents for 20 kW LP

Page 1: ...uct support lookup Pour le fran ais visiter http www generac com service support product support lookup 000918 Register your Generac product at WWW GENERAC COM 1 888 GENERAC 888 436 3722 000209a WARNI...

Page 2: ...nt checked periodically by an IASD Normal maintenance service and replacement of parts are the responsibility of the owner operator and are not considered defects in materials or workmanship within th...

Page 3: ...e Menu Displays 13 The LCD Panel 13 Menu System Navigation 14 Setting the Exercise Timer 16 Battery Charger 16 Manual Transfer Operation 17 Transfer to Generator Power Source 17 Transfer to Utility Po...

Page 4: ...Table of Contents iv Owner s Manual for 60 Hz Air Cooled Generators Section 5 Troubleshooting Quick Reference Guide Generator Troubleshooting 31 Quick Reference Guide 32...

Page 5: ...e manufacturer strongly recommends that if the operator is also the owner to read the owner s manual and thoroughly understand all instructions before using this equipment The manufacturer also strong...

Page 6: ...rm wiring and connections to unit Failure to follow proper installation requirements could result in death serious injury and damage to equipment or property 000115 WARNING Moving Parts Do not wear je...

Page 7: ...ath or serious injury 000150 DANGER Electrocution Never connect this unit to the electrical system of any building unless a licensed electrician has installed an approved transfer switch Failure to do...

Page 8: ...rged or improperly rated fire extinguishers will not extinguish electrical fires in automatic standby generators 000100a WARNING Consult Manual Read and understand manual completely before using produ...

Page 9: ...with Cover E Exhaust Enclosure J Oil Filter N Fuel Regulator B Main Line Circuit Breaker Generator Disconnect F Oil Fill Cap Dipstick K Oil Drain Hose O Fuel Inlet C Control Panel G Status LED Indica...

Page 10: ...Compartment Battery not supplied J Oil Fill Cap N Sediment Trap B Main Line Circuit Breaker Generator Disconnect F Exhaust Enclosure K Oil Filter O Fuel Regulator C Airbox with Air Cleaner G Status L...

Page 11: ...nded When operated above 77 F 25 C there may be a decrease in engine power See Engine These generators are rated in accordance with UL 2200 Safety Standard for Stationary Engine Generator Assemblies a...

Page 12: ...ication The Emission Control System on this generator consists of the following Fuel Requirements The engine has been fitted with a dual fuel carburetion system The unit will run on natural gas or LP...

Page 13: ...bottom of the new air cooled generators This offers a sleek contoured appearance as well as offering protection from rodents and insects by covering the lifting holes located in the base Requires use...

Page 14: ...General Information 10 Owner s Manual for 60 Hz Air Cooled Generators This page intentionally left blank...

Page 15: ...d will be locked A set of keys is attached to the intake side of the generator 1 Cut the plastic bag to remove the keys 2 Use the keys to open the lid of the generator NOTE The enclosed keys provided...

Page 16: ...priately sized padlock not included with a shackle long enough to pass through both lock tabs B Figure 3 3 Main Breaker NOTE DO NOT lock out the MLCB during normal generator operation Doing so will co...

Page 17: ...running under generator power utility is lost OFF This button shuts down the engine and prevents automatic operation of the unit MANUAL This button cranks and starts the generator Transfer to standby...

Page 18: ...NG or LP Firmware Update Insert USB Alarm Log Alarm Log Run Log 1 thru 50 1 thru 50 Warning Message s Charger Warning Charger Missing AC Low Battery Battery Problem Exercise Set Error USB Warning Down...

Page 19: ...XXX USB V XXXX Are You Sure Yes or No ESC ENTER ESC ENTER ESC ENTER Select Yes then Press Enter to continue or Press ESCAPE to escape out of updating During update process the Blue Manual light flashe...

Page 20: ...n the fuse is removed Table 3 1 details the exercise information and programming options for all Home Standby Generators Figure 3 8 illustrates the engine speed profile during a typical exercise cycle...

Page 21: ...load Disconnect transfer switch from all power sources prior to manual transfer Failure to do so will result in death or serious injury and equipment damage 002565 A MANUAL Will not transfer to genera...

Page 22: ...or disconnect to ON CLOSED The generator will start automatically when utility source voltage drops below a preset level Loads are transferred to the standby power source after the unit starts Automat...

Page 23: ...mal genera tor voltage output is determined to be low During this cycle the generator controller will display Warming Up on the display screen The generator controller display will show Under Voltage...

Page 24: ...Operation 20 Owner s Manual for 60 Hz Air Cooled Generators This page intentionally left blank...

Page 25: ...y charger cable Figure 4 1 Disconnecting Battery Charger Cable Performing Scheduled Maintenance It is important to perform maintenance as specified in the Service Schedule for proper generator operati...

Page 26: ...e air filter Clean Check gap Replace spark plugs Inspect adjust valve clearance Inspect clean sediment trap Consult local codes and guidelines Contact the nearest IASD for assistance if necessary Remo...

Page 27: ...he generator to ON CLOSED 4 The system is now operating in automatic mode The main utility disconnect can be turned ON CLOSED Engine Oil Requirements To maintain the product warranty the engine oil sh...

Page 28: ...pter Tighten the filter an additional 3 4 to one full turn 7 Refill the engine with the proper recommended oil See Engine Oil Requirements 8 Press the MANUAL button on the control panel to start the e...

Page 29: ...or service assistance Proper valve clearance is essential for prolonging the life of the engine Check Valve Clearance NOTE The engine should be cool before checking the valve clearance Adjustment is n...

Page 30: ...the Service Schedule Contact an IASD for assistance if necessary Proceed as follows to inspect the battery 1 Press the OFF button to shut down the generator then lift the lid and remove the front pane...

Page 31: ...Sediment Trap The sediment trap removes contaminants moisture and fine particles from gaseous fuels before they enter the fuel regulator Accumulated moisture and particles must be emptied from the sed...

Page 32: ...rankcase with oil 9 Attach a tag to the engine indicating the viscosity and classification of the new oil in the crankcase 10 Remove the spark plug s and spray a fogging agent into the spark plug s th...

Page 33: ...check gap replace plug s as needed 3 Confirm fuel pressure to regulator is 10 12 in water column 19 22 mm Hg for LP and 3 5 7 0 in water column 9 13 mm Hg for natural gas 4 Turn fuel conversion valve...

Page 34: ...ED Unit will not start in AUTO with utility loss Check the LEDs screen for alarms Check oil level and add oil as needed If oil level is correct contact an IASD RPM SENSE LOSS RED Unit will not start i...

Page 35: ...trol panel displays CHECK BATTERY replace the battery BATTERY PROBLEM YELLOW Yellow LED illuminated in any state Check the screen for additional information Contact an IASD CHARGER WARNING YELLOW Yell...

Page 36: ...Troubleshooting Quick Reference Guide 34 Owner s Manual for 60 Hz Air Cooled Generators This page intentionally left blank...

Page 37: ...Troubleshooting Quick Reference Guide Owner s Manual for 60 Hz Air Cooled Generators 35 This page intentionally left blank...

Page 38: ...Troubleshooting Quick Reference Guide 36 Owner s Manual for 60 Hz Air Cooled Generators This page intentionally left blank...

Page 39: ......

Page 40: ...ights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290...

Reviews: