Remote Annunciator

ERROR HANDLING

 

‹

An error will be reported by flashing the Communication OK light—
the rate of flashing will be indicative of the cause of the error.
1.  No reply from generator control system— frequency one sec-

ond on/one second off.

2.  Consecutive data errors— frequency 0.5 seconds on/two sec-

onds off.

The Annunciator, if configured for auto-baud rate detect, will try 
several times at each of four different baud rates (57.6K, 38.4K, 
9600 and 4800) before reporting a communication error by de-
energizing all the relays and then flashing the Communication OK 
light.

LIMITS OF OPERATION

 

‹

The following communication restrictions apply for multiple units 
on a common RS485 line:

A maximum of 15, 1000 ohm RS485 Loads (i.e. 57.6K 

•  

Annunciator, G-panel, H-panels, etc) can be connected to the 
RS485 bus at one time. 

NOTE:

14.   There MUST be only ONE (1) master in the RS485 com-

munication bus. All others must be slaves (PASSIVE).

TERMINOLOGY & ABBREVIATIONS

GUI 

-   Graphical User Interface for Windows based comput-

ers

MPS 

-  Modular Power System

PM-GC  -   Power Manager – Generator Controller (controls a 

single Generator)

PM-SC  -   Power Manager – System Controller (used to control 

multiple Generators)

LEDs 

-  Light Emitting Diodes

GenLink  -  Generator communication system
ILC 

-  Integrated Logic Controller

RRP 

-   Remote Relay Panel (Relays with no LEDs/Keypad), 

0G5720

RAP 

-   Remote Annunciator Panel (LEDs/Keypad without 

Relays J1 - J8), 0G5721

Summary of Contents for 0G5719

Page 1: ...21 light Remote Annunciator Owner s M anual...

Page 2: ...Interface GUI available using a computer via the RS232 connector on the annunciator printed circuit board see Figure 2 Relays J1 J8 provides a set of normally open contacts All relays are energized c...

Page 3: ...he same wire grouping as any high voltage or high current conductors 2 The generator control panel Baud Rate should be selected to be compatible with other components that are connected to the RS485 c...

Page 4: ...ciator to provide strain relief for the connecting cables and wires Figure 3 RELAY ANNUNCIATION J1 J8 The user can select up to eight of the following 18 generator parameters to annunciate via the rel...

Page 5: ...Figures 6 and 7 DIP Parameter Relay 1 1 RPM Sensor Loss 1 1 3 Overspeed 2 1 5 High Water Temp Low Water Level 3 1 10 Pre Low Fuel 4 Figure 6 S1 Figure 7 S2 Example 2 If subsequently DIP1 3 is removed...

Page 6: ...ht to turn ON This shows whether the load is power by the utility For an engine controller that is part of an MPS system line power is not used PARAMETER BATTERY CHARGER AC FAILURE This light LED annu...

Page 7: ...nication between the Remote Annunciator Panel and the Generator control system It typically requires less than a minute for the Annunciator to determine the correct baud rate and connect to the RS485...

Page 8: ...his method allows for the connection of more than one Annunciator In Master mode the Annunciator is the Modbus master and will request data from the PM GC or PM SC The PM GC or PM SC must be set as a...

Page 9: ...setting the Annunciator functions A GenLink serial cable P N 0F7707 should be used to connect a laptop computer s RS232 serial port to the Annunciator DB9 connector The GenLink cable is a Null Modem...

Page 10: ...he following communication restrictions apply for multiple units on a common RS485 line A maximum of 15 1000 ohm RS485 Loads i e 57 6K Annunciator G panel H panels etc can be connected to the RS485 bu...

Page 11: ...to normally port 0 and look to see if the check boxes change state If not data is not being transmitted received check the cabling If data is being received check the baud rate settings of all connec...

Page 12: ...Part No 0G6960 Revision C 09 14 09 Printed in U S A...

Reviews: