Section 3: Installation
8
Homelink Upgradeable Manual Transfer Switch Owner’s Manual
5.
Remove the lower left screw that secures the
divider plate in the transfer switch (B in
6.
Install the new automatic back plate in the transfer
switch and secure to the transfer switch enclosure
(C in
Figure 3-3.
Figure 3-4.
7.
Remove the neutral conductor from the main lug
on the neutral bar.
8.
Terminate the normal power neutral to the main lug
on the neutral bar (D in
9.
Terminate the neutral conductor from the generator
power feeder onto the neutral terminal bar in the
transfer switch (E in
10.
Terminate the normal power feeder conductors to N1
and N2 on the transfer mechanism (F in
).
11.
Terminate the panelboard feeder conductors to T1
and T2 on the transfer mechanism (G in
).
12.
Terminate the generator feeder conductors to E1
and E2 on the transfer mechanism (H in
).
13.
Terminate generator control wiring to the N1, N2,
T1, 23 and 194 terminals in the transfer switch (J in
).
14.
Install the new panelboard cover and properly label
all branch circuits.
15.
See Section 4
(Automatic HSB Generator Only)
to verify proper
transfer switch and generator operation.
Figure 3-5.
000976
A
000976
B
C
000989
F
D
E
G
H
J
Summary of Contents for 006852