6
Figure 6 - Generator Controls
14
10
15
16
7
2.2 CONNECTION PLUGS
2.2.1 120 VAC, 20 AMP, DUPLEX RECEPTACLE
This is a 120 Volt outlet protected against overload by a 20 Amp
push-to-reset circuit breaker (Figure 7). Use each socket to power
120 Volt AC, single phase, 60 Hz electrical loads requiring up to a
combined 2400 watts (2.4 kW) or 20 Amps of current. Use only
high quality, well-insulated, 3-wire grounded cord sets rated for
125 Volts at 20 Amps (or greater).
Keep extension cords as short as possible, preferably less than
15 feet long, to prevent voltage drop and possible overheating of
wires.
Figure 7 - 120 Volt AC, 20 Amp, Duplex Receptacle
2.2.2 120/240 VAC, 20 AMP RECEPTACLE
Use a NEMA L14-20R plug with this receptacle (rotate to lock/
unlock). Connect a suitable 4-wire grounded cord set to the plug
and to the desired load. The cord set should be rated for 250 Volts
AC at 20 Amps (or greater) (Figure 8).
Figure 8 - 120/240 VAC, 20 Amp Receptacle
120V/240V
20A
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase
loads requiring up to 2400 watts (2.4 kW) of power at 30 Amps or
240 Volt AC, 60 Hz, single phase loads requiring up to 3250 watts
(3.25 kW) of power at 13.5 Amps. The outlet is protected by two
15 Amp push-to-reset circuit breakers.
2.3 HOW TO USE THE GENERATOR
See the "To Start the Engine" section for how to safely start and
stop the generator and how to connect and disconnect loads. If
there are any problems operating the generator, please call the
generator helpline at 1-888-436-3722.
Never operate in an enclosed area or indoors!
NEVER use in the home, in a vehicle, or in
partly enclosed areas such as garages, EVEN
IF doors and windows are open! ONLY use
outdoors and far from open windows, doors,
vents, and in an area that will not accumulate
deadly exhaust.
The engine exhaust fumes contain carbon
monoxide, which you cannot see or smell.
This poisonous gas, if breathed in sufficient
concentrations, can cause unconsciousness or
even death.
Adequate, unobstructed flow of cooling and
ventilating air is critical to correct generator
operation. Do not alter the installation or permit
even partial blockage of ventilation provisions,
as this can seriously affect safe operation
of the generator. The generator MUST be
operated outdoors.
This exhaust system must be properly
maintained. Do nothing that might render the
exhaust system unsafe or in noncompliance
with any local codes and/or standards.
Always use a battery operated carbon
monoxide alarm indoors, installed according to
the manufacturer's instructions.
Operation