8
PowerBoss 5,500 Watt Storm-Plus Generator
RECEPTACLES
120/240 Volt AC, 30 Amp, Locking
Receptacle
Use a NEMA L14–30 plug with this receptacle. Connect a
4–wire cord set rated for 250 Volt AC loads at 30 Amps (or
greater) (Figure 7).You can use the same 4–wire cord if you
plan to run a 120 Volt load.
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 3,600 watts of power at
30 Amps for 120 Volts; 5,500 watts of power (5.5 kW) at
30 Amps for 240 Volts.The outlet is protected by a 20 Amp
push–to–reset circuit breaker.
CAUTION!
Although this outlet states it has a
120/240 Volt 30 Amp rating (up to 7,200 watts), the
generator is only rated for 5,500 watts. Powering
loads that exceed the wattage/amperage capacity of
the generator can damage it or cause serious injuries.
120 Volt AC, 20 Amp, Duplex
Receptacles
Each receptacle (Figure 8) is protected against overload by
a 20 Amp push–to–reset circuit breaker.
Use each receptacle to operate 120 Volt AC, single–phase,
60 Hz electrical loads requiring up to 2,400 watts (2.4 kW)
at 20 Amps of current. Use cord sets that are rated for
125 Volt AC loads at 20 Amps (or greater).
Figure 7 — 120/240 Volt AC, 30 Amp, Locking Receptacle
Figure 8 — 120 Volt, 20 Amp Duplex Receptacle
Summary of Contents for PowerBoss 5500 Watt Storm Plus
Page 13: ...PowerBoss 5 500 Watt Storm Plus Generator 13 NOTES ...
Page 14: ...14 PowerBoss 5 500 Watt Storm Plus Generator SCHEMATIC ...
Page 15: ...PowerBoss 5 500 Watt Storm Plus Generator 15 WIRING DIAGRAM WARNING TAB MUST NOT BE BROKEN ...
Page 16: ...16 PowerBoss 5 500 Watt Storm Plus Generator EXPLODED VIEW MAIN UNIT ...
Page 29: ...29 PowerBoss 5 500 Watt Storm Plus Generador NOTAS ...