www.gemu-group.com
25 / 32
GEMÜ 1242
DeviceNet
Class
Inst.
Attr.
Parameter
Lengt
h
Data
type
Ac-
cess
Stand-
ard
value
Value range
Fh
17h
1h
Programming error
1 byte
USINT
Get
1
0 = Programming OK
1 = not calibrated
2 = no stroke
3 = stroke < min. stroke
4 = Sensor error position
closed
5 = Sensor error position open
6 = Sensor error position
open
Fh
19h
1h
Internal error
1 byte
USINT
Get
0
0 = Device OK
1 = un-valid crc-check
2 = un-valid serial number
3 = Memory error
Fh
1Ah
1h
Stroke reduction warning
1 byte
USINT
Get
0
0 = Stroke OK
1 = Stroke reduction position
closed
2 = Stroke reduction position
open
3 = Stroke reduction position
open
Fh
1Bh
1h
Valve cycles user
4 byte
UDINT
Get/Set 0
Resettable to 0,
display of numerical values 0 -
429496729
Fh
1Ch
1h
Valve cycles total
4 byte
UDINT
Get
0
Display of numerical values 0 -
429496729
Specific data - DeviceNet