PROGRAMMING PARAMETERS

Error Messages:
Fail:

 Sensor failure or sensor selection wrong

E.FLS:

 Hardware failure

E.CAL:

 Hardware failure

E.EPr:

 Memory failure

Gürbüzo

ğ

lu Elektronik San. ve Tic. Ltd. 

Ş

ti.

http://www.gemo.com.tr.

Çamlıtepe Cad. No:297 / 3-4 Siteler, Ankara, Türkiye

e-posta: [email protected]

Tel: +90-312-3503900, Fax: +90-312-3511117

3

SET

H.hys

0 .. 50 

o

C

SET

Heat Hysteresis (

o

C):

PID is active if set to 0

A.hys

SET

Pb.C

5 .. 150 

o

C

SET

Ct

1 .. 200 sec

SET

oFFS

SET

td

SET

+

CodE

Enter 162

SET

UP.L

Lo.L ..

Upper Scale (

o

C) 

SET

Upper limit value for Lo.L,
H.SET and A.SET. Upper
Scale value differs according
to the selected sensor type.

AL.tY

SET

r.ALr/

b.ALr

SET

ti

0:00 .. 30:00

min:sec

SET

Lo.L

Lower Scale ..

UP.L (

o

C) 

SET

Lower limit value for UP.L,
H.SET and A.SET. Lower Scale value
differs according to the selected
sensor type.

H.Hys

not  0

Back

Press “Back”

to return to the 

top of  

parameters 

programming 

block

Integral Time: in min:sec
If set to 0:00, P, PD is
active (integral OFF).

Derivative Time: in min:sec.
If set to 0:00, P, PI is
active (derivative OFF).

Alarm Hysteresis (

o

C)

Proportional Band in (

o

C)

Control period (sec)

Offset Value; Offset is directly added
to the measured value. This feature shall
be used for user calibration. Normally set to 0.

Enter 162 to pass
to parameter prog. mode

Relative or band Alarm
Value. Displayed if AL.ty is
other then Abs or –Abs. 

Press for 2 sec.

Upper Display

Abs,rel,bnd,bn.i

-Abs,-rel,

-bnd,-bn.i,

SnS.O, SnS.F 

Alarm Type:
Abs: Absolute         -Abs: Absoloute, invert out   SnS.O: Sensor failure 
rel: Relative             -rel: Relative, invert out         Continuous out
bnd: band                -bnd: band, invert out            SnS.F: Sensor failure
bn.i: band inhibit     -bn.i: band, invert out            Flashing out

CodE

Enter “262”

to start

auto-tune

SET

Upper Display

“tunE”

flashes

 Before starting Auto-tune, adjust H.SET.

 Process value may exceed H.Set during auto-tuning.

 After auto-tuning, control form automatically switches

  to PID mode.

 Auto-tuning is stopped (interrupted) any time by 

  pressing any key. In this case, the parameters before
  auto-tuning is valid.

 Auto-tuning may not always determine the best values

  for your process.

Factory SET Values:
H.SEt: 100 

o

C

A.SEt: 400 

o

C

H.hys: 0 

o

C

A.hys: 3 

o

C

Pb.C: 30 

o

C

Ct: 4 sec
ti: 5:00 min:sec
td: 1:00 min:sec
UP.L: 400 

o

C

Lo.L: 0 

o

C

oFFS: 0 

o

C

AL.tY : rel
r.ALr: 3 

o

C

C-t: 0.0 

o

C / min

L.dSP: yes
o.Sht: oFF
SECU: AH

1 .. 50 

o

C

0:00 .. 10:00

min:sec

-100 .. 100 

O

C

-100 .. 100 

O

C-t

0.0 .. 300.0

o

C / min

SET

If C-t is not 0, ramping starts after power on. SET value
is incremented or decremented C-t degrees per minute
until SET reaches H.SEt or C.SEt.

CodE

Enter “555”

for factory

reset

SET

“YES” / “nO”

 To return to factory settings:
 Code > 555 > select “yes” > 
 Press “SET” 

Upper Display

yes: Lower display ON
no: Lower display OFF

SET

L.dSP

yes .. no

AL.tY=

 Abs,-Abs,

SnS.O,

SnS.F

End Prog.

o.Sht

OFF, 10.0,

5.0, 3.0,

1.0, 0.2

SET

SECU

AH, -H, A-, --

SET

AH: ALARM SET and HEAT SET may be SET,
-H : Only HEAT SET may be SET,
-A : Only ALARM SET may be SET,
-- : ALARM SET and HEAT SET may not be SET.

Over shoot reduction: All options other than “OFF” may help  to reduce over 
shoot more but also may increase instability around SET point. For this reason;
First try “OFF” option then 10.0->5.0->3.0->1.0->0.2 options if needed.
Options 1.0 and 0.2 are most sensitive and may result more instability around 
SET point among other options. With this parameter, over shoot is not allowed
more than; OFF: not limited, 10.0: 10 , 5.0: 5 , 3.0: 3 , 1.0: 1 , 0.2: 0.2 degrees 
(over SET point).

H.Hys

not  0