GEMO

PROGRAMMING HEAT SET and ABSOLUTE ALARM SET

ALARM OUTPUT

PV

ALARM

AL.tY= -Abs, -rel

AL.tY = Abs, -Abs; X = A.SEt
AL.tY = rel, -rel     ; X = H.SEt + r.ALr

X

(X+A.hys)

PV

ALARM

AL.tY=Abs, rel

X

(X-A.hys)

ON

ON

C

PV

A = H.Set-b.Alr,  B = H.SET-b.Alr+A.hys,   C = H.SEt+b.Alr-A.hYS,  D = H.SET+b.Alr

D

B

A

ON

C

PV

D

B

A

ON

AL.tY= bnd, bn.i (*)

AL.tY= -bnd (**)

ON

H.SEt

H.SEt

ALARM

ALARM

(*)   AL.tY = bn.i is same as  bnd except that if AL.tY = bn.i, ALARM is never ON before PV is in band.
(**)  AL.tY = -bn.i is always same as -bnd.

AL.ty = SnS.O:

 If sensor measurement fails; Alarm out is continuously ON.

AL.ty = SnS.F:

 If sensor measurement fails; Alarm out is flashing (1 second ON then 2 seconds OFF, periodically).

(ON-OFF CONTROL)

ON-OFF is active when 

“H.Hys”

 is other then 0

H.SET

(H.SET-H.Hys)

PV

OUT

H.SET

(H.SET+C.Hys)

Heating

Cooling

PID PARAMETERS

- P, PI, PD, PID

 is active when 

“H.Hys”

 is set to 0 (only for heating; h-C is set to ”HEAt”)

- PbC: 

Proportional band in oC.

- Ct: 

Control period for PID control. Prefer 4-10 sec.

- Ti:

 Integral time; Set in minutes. Determines how fast controller reacts to compensate the offset between SET point and the 

process value. If set to 0, integral part is OFF. If set too low, process value may oscillate.
-

 Td:

 Derivative time; Set in minutes. If set to 0, derivative part is OFF. Determines how sensitive the controller is to changes of 

the offset between SET point and the process value. If set too high, process value may oscillate or overshoot.

CLAEANING

Do not use any solvents (alcohol, thinners, benzine, acid, etc.) or corrosive substances to clean the device. Use only a dry 
and clean non-abrasive cloth. Before cleaning, disconnect the power supply and mains connections.

Gürbüzo

ğ

lu Elektronik San. ve Tic. Ltd. 

Ş

ti.

http://www.gemo.com.tr.

Çamlıtepe Cad. No:297 / 3-4 Siteler, Ankara, Türkiye

e-posta: [email protected]

Tel: +90-312-3503900, Fax: +90-312-3511117

4

Press 2 sec.

SET

H.SEt

Lo.L .. UP.L 

o

C

Prog. end

Upper Display

SET

A.SEt

Lo.L .. UP.L

o

C

SET

Heat SET;
(Process SET)
value is
set Lo.L .. UP.L

Displayed if Ab.AL=Yes; 
Absolute Alarm SET 
Value is set Lo.L .. UP.L

AL.tY
= rel, -rel
bnd, -bnd
bn.i, -bn.i,
SnS.O,
Sn.F