GEMO

PROGRAMMING HEAT SET

SET

Press SET

Read SET

value

0..400 

o

C

End

Display

Process

Value

Display

PROGRAMMING HYSTERESIS (hYS), PROPORTIONAL BAND (PbC) and

CONTROL PERIOD (Ct)

Press SET

at Power ON

hYs

hYs / 0..20 

o

C

Display

PbC

Ct

SET

SET

0.....20

PbC / 1..30 

o

C

Display

SET

1.....30

Ct / 10..240 sec

Display

SET

10.....240

Wait

5 sec

Wait

5 sec

Wait

5 sec

End

Process Value

Display

FACTORY SETTINGS

Hys

3

 o

C

PbC

12

 o

C

Ct

30 sec.

ERROR MESSAGE

or: Displays “or” message in case of sensor failure, measurement out of range or 
hardware fails to measure input signal.

Gürbüzo

ğ

lu Elektronik San. ve Tic. Ltd. 

Ş

ti.

http://www.gemo.com.tr

Çamlıtepe Cad. No:297 / 3-4 Siteler, Ankara, Türkiye

e-posta: [email protected]

Tel: +90-312-3503900, Fax: +90-312-3511117

3

Summary of Contents for AT961

Page 1: ...ailure measurement out of range or hardware fails to measure input signal Supply Voltage 100 240VAC 50 60Hz Power Consumption 6VA Humidity 80 up to 30o C then linearly decreases to 50 at 50o C non condensing Altitude 2000 m EMC EN 61000 6 1 EN 61000 6 3 Only light industrial environment Safety EN 61010 1 Pollution degree 1 measurement category I Only light industrial environment double reinforced ...

Page 2: ...e device in a well ventilated place Install the device permanently into a proper panel cut out Fix the device with two fasteners supplied with the device Only front panel must be accessible after installation is completed Do not operate the device other then the environmental conditions given in Technical Specification Do not operate the device in environments that may cause conductive pollution T...

Page 3: ...ay SET 1 30 Ct 10 240 sec Display SET 10 240 Wait 5 sec Wait 5 sec Wait 5 sec End Process Value Display FACTORY SETTINGS Hys 3 o C PbC 12 o C Ct 30 sec ERROR MESSAGE or Displays or message in case of sensor failure measurement out of range or hardware fails to measure input signal Gürbüzoğlu Elektronik San ve Tic Ltd Şti http www gemo com tr Çamlıtepe Cad No 297 3 4 Siteler Ankara Türkiye e posta ...

Page 4: ... proportional control SET SET PbC PV HEAT SET 2 CLAEANING Do not use any solvents alcohol thinners benzine acid etc or corrosive substances to clean the device Use only a dry and clean non abrasive cloth Before cleaning disconnect the power supply and mains connections Gürbüzoğlu Elektronik San ve Tic Ltd Şti http www gemo com tr Çamlıtepe Cad No 297 3 4 Siteler Ankara Türkiye e posta info gemo co...

Reviews: