&20%867,21&21752/
6HWWLQJWDEOH
Set the gas flow with an analyser in order to obtain
the CO/CO
2
ratios that are indicated in the following
table.
Combustion product evacuation outlet back pressu-
re: 0 mmCE.
P1 and P2 values may be more or less high accor-
ding to whether back pressure is greater or smaller.
0RGHOV
7+5&
7+5&6
Useful power
30/50 °C
60/80 °C
mini/maxi
mini/maxi
kW
kW
10.6 / 101.0
9.5 / 94.0
Maximum heat-generating flow
kW
10 / 100
∅
Gas regulation plate
Nat Gas H
Propane
mm
mm
7.30
5.60
∅
Air ring
Nat Gas H
Propane
mm
mm
-
31
Gas flow (15 °C 1013 mbar)
Nat Gas H G20
Propane G31
m
3
/h
kg/h
1.06 / 10.58
0.776 / 7.762
Gas pressure P2
Nat Gas H
Propane
mbar
mbar
0.40 / 6.00
0.40 / 6.20
Servo-system air pressure (PL)
Nat Gas H
Propane
Pa
Pa
40 / 610
40 / 630
CO
2
Emission
Nat Gas H
Propane
%
%
7.5 - 8.0 / 9.0 - 9.5
10.0 - 10.5 / 10.5 - 11
CO Emission
Nat Gas H
ppm
0 / 20
No
x
Emission
Nat Gas H
ppm
20 / 25