- 20 -
PARAMETER LIST
C
621
Konfig-
Ausgang3R
Function output3 clip-in function module
0: Default (function according to the hydraulic
diagram)
1: Status output,
2: Alarm output
3: Operational signal
4: Switching off external transformer
5: Pump of the second heating circuit
6: DHW circulating pump
7: Actuating device with warm air curtain
activated
8: Pump of the pressureless header
9: Basic function of controller clip-in module
10: Basic function K2,
11: Actuating device with full DHW charging
activated, in connection with stratification
storage tanks,
12: Actuating device when analog signal (at the
clip-in function module) has exceeded the
threshold
0...255 2
2
2
2
LPB : LPB Clip-in
C
605
LPBAdrGerNr LPB device number of LMU
0...255
1
1
1
1
C
606
LPBAdrSegNr LPB segment number of LMU
0...14
0
0
0
0
Level Line
Display
Function
Range
Factory setting : boiler version
0.9-9
2-13/2-17
5-25
10-50
Level
Line
Display
Function
Unit
C
700
Stoer1
1st past value of lockout code counter
-
C
701
StrPn1
1st past value of lockout phase
-
C
702
StrDia1
1st past value of internal diagnostic code
-
C
728
StrAlba1
1st past value of ALBATROS error code
-
C
703
Stoer2
2nd past value of lockout code counter
-
C
704
StrPn2
2nd past value of lockout phase
-
C
705
StrDia2
2nd past value of internal diagnostic code
-
C
729
StrAlba2
2nd past value of ALBATROS error code
-
C
706
Stoer3
3rd past value of lockout code counter
-
C
707
StrPn3
3rd past value of lockout phase
-
C
708
StrDia3
3rd past value of internal diagnostic code
-
C
730
StrAlba3
3rd past value of ALBATROS error code
-
C
709
Stoer4
4th past value of lockout code counter
-
C
710
StrPn4
4th past value of lockout phase
-
C
711
StrDia4
4th past value of internal diagnostic code
-
C
731
StrAlba4
4th past value of ALBATROS error code
-
C
712
Stoer5
5th past value of lockout code counter
-
C
713
StrPn5
5th past value of lockout phase
-
C
714
StrDia5
5th past value of internal diagnostic code
-
C
732
StrAlba5
5th past value of ALBATROS error code
-
C
715
Stoer-akt
Current value of lockout code counter
-
C
716
StrPn-akt
Current value of lockout phase
-
C
717
StrDia-akt
Current value internal diagnostic code
-
C
733
StrAlba_akt
Current value of ALBATROS error code
-
C
724
MmiStatus
Selection of summer / winter operating modes
0-255
C
725
SwVersion-LMU
SW version of LMU for presentation on the OT parameter setting level
-
C
755
IonStrom
Measured value of ionization current
µ
A