Upstream of the GEMÜ 3030
m
Flow no free
outlet is allowed to ensure that the pipeline
is always completely
fi
lled.
Correct
Flow
Incorrect
Flow
In addition, the
fl
owmeter must be installed
in a horizontal mounting position at the side
of the area de
fi
ned below.
Preferred installation position
Non-recommended installation position
Danger of trapped air
Danger of solid matter
deposits
In order to avoid turbulence as a result
of pipe bending which can falsify the
measurement results, a straight inlet
distance of 10 x DN and a straight outlet
distance of 5 x DN should be planned.
Flow
The electronics housing with display can be
rotated through 370°.
X3
1
5
4
3
2
For plant-speci
fi
c reasons earth potential
di
ff
erences between pipeline and reference
earth may occur. Earth the pipeline before
and after the
fl
owmeter to eliminate these
di
ff
erences.
Important:
To guarantee the measuring
accuracy, the GEMÜ 3030
m
Flow
must be installed in the
fi
lled
pipeline at least 24 hours before
measurement.