24
ADV50 QS, SW-PW V1.11 / CTL V2.11
Italiano
English
Italiano
English
Pr.
Explanation
Settings
Factory
Setting
NOTE
10.01
Input Terminal for PID
Feedback
0: Positive PID feedback from external terminal
AVI (0 ~ +10VDC)
1: Negative PID feedback from external terminal
AVI (0 ~ +10VDC)
2: Positive PID feedback from external terminal
ACI (4 ~ 20mA)/ AVI2 (0 ~ +10VDC).
3: Negative PID feedback from external terminal
ACI (4 ~ 20mA)/ AVI2 (0 ~ +10VDC).
0
a
10.02
Proportional Gain (P) 0.0 to 10.0
1.0
a
10.03
Integral Time (I)
0.00 to 100.0 sec (0.00=disable)
1.00
a
10.04
Derivative Control (D) 0.00 to 1.00 sec
0.00
10.05
Upper Bound for
Integral Control
0 to 100%
100
10.06
Primary Delay Filter
Time
0.0 to 2.5 sec
0.0
10.07
PID Output Freq Limit 0 to 110%
100
10.08
PID Feedback Signal
Detection Time
0.0 to 3600 sec (0.0 disable)
60.0
10.09
Treatment of the
Erroneous PID
Feedback Signals
0: Warn and RAMP to stop
1: Warn and COAST to stop
2: Warn and keep operation
0
10.10
Gain Over the PID
Detection Value
0.0 to 10.0
1.0
a
10.11
Source of PID Set
point
0.00 to 600.0Hz
0.00
10.12
PID Offset Level
1.0 to 50.0%
10.0
10.13
Detection Time of PID
Offset
0.1 to 300.0 sec
5.0
10.14
Sleep/Wake Up
Detection Time
0.0 to 6550 sec
0.0
10.15
Sleep Frequency
0.00 to 600.0 Hz
0.00
10.16
Wakeup Frequency
0.00 to 600.0 Hz
0.00
10.17
Minimum PID Output
Frequency Selection
0: By PID control
1: By minimum output frequency (Pr.01.05)
0
Group 11 Parameters for Extension Card
11.00
Multi-function Output
Terminal MO2/RA2
0
11.01
Multi-function Output
Terminal MO3/RA3
0
11.02
Multi-function Output
Terminal MO4/RA4
0
11.03
Multi-function Output
Terminal MO5/RA5
0
11.04
Multi-function Output
Terminal MO6/RA6
0
11.05 Multi-function
Output
Terminal MO7/RA7
0: No function
1: AC drive operational
2: Master frequency attained
3: Zero speed
4: Over torque detection
5: Base-Block (B.B.) indication
6: Low-voltage indication
7: Operation mode indication
8: Fault indication
9: Desired frequency 1 attained
10: Terminal count value attained
11: Preliminary count value attained
12: Over Voltage Stall supervision
13: Over Current Stall supervision
14: Heat sink overheat warning
15: Over Voltage supervision
0