7
81085_G-Vision 66_12-2021_ENG
3. TECHNICAL SPECIFICATIONS
Touchscreen technology Back-up battery
Projected capacitive
3V 50mAh Lithium, rechargeable, not user-replaceable, model VL2330.
Fuse
Automatic
Serial Port
RS-232, RS-485, RS-422 software configurable
Flash
4GB
RAM
2GB
Hardware clock
Clock/Calendar with back-up battery
Accuracy RTC (at 25°C)
<100ppm
ENVIRONMENTAL CONDITIONS
Operating temperature
(surrounding air temperature)
-20 ÷ +60°C (vertical installation) Plug-in
modules and USB devices may limit max
temperature to +50°C
EN 60068-2-14
Storage temperature
-20 ÷ +70°C
EN 60068-2-1
EN 60068-2-2
EN 60068-2-14
Operating and storage humidity
5 ÷ 85 % RH not-condensing
EN 60068-2-30
Vibrations
5 ÷ 9 Hz, 7 mm p-p
9 ÷ 150 Hz, 1 g
EN 60068-2-6
Shock
± 50 g, 11 ms, 3 pulses per axis
EN 60068-2-27
Protection class
Front panel IP66, Rear IP20
EN 60529
ELECTROMAGNETIC COMPATIBILITY (EMC)
Radiated disturbance test
Class A
CISPR 22
CISPR 16-2-3
Electrostatic discharge immunity test
8 kV (air electrostatic discharge)
4 kV (contact electrostatic discharge)
EN 61000-4-2
Radiated, radio-frequency,
electromagnetic field immunity test
80 MHz ÷ 1 GHz, 10V/m
1,4 GHz ÷ 2 GHz, 3 V/m
2 GHz ÷ 2.7 GHz, 1 V/m
EN 61000-4-3
Burst immunity test
± 2 KV dc power port
± 1 KV signal line
EN 61000-4-4
Surge immunity test
± 0,5 KV dc power port (line to earth)
± 0,5 KV dc power port (line to line)
± 1 KV signal line (line to earth)
EN 61000-4-5
Immunity to conducted disturbances inducted
by radiofrequency field
0.15 ÷ 80 MHz, 10V
EN 61000-4-6
Power frequency magnetic field immunity test
Enclosure, 50/60Hz, 30A/m
EN 61000-4-8
Voltage dips, short interruptions and voltage
variations immunity test
Port: AC mains; Level:
100% duration:
1 cycle and 250 cycles (50Hz);
1 cycle and 300 cycles (60Hz);
40% duration:
10 cycles (50Hz);
12 cycles (60Hz);
70% duration:
25 cycles (50Hz);
30 cycles (60Hz);
Phase: 0°-180°
Test executed on the 230Vac side of the
Gefran Soluzioni Srl Power Supply
EN 61000-4-11
Port: DC mains; Level:
0% duration:
10ms 20 spaces by 1s
Test executed on the 24Vdc of the EUT
EN 61000-4-29