![gefran EXP-D20A6 Instruction Manual Download Page 7](http://html.mh-extra.com/html/gefran/exp-d20a6/exp-d20a6_instruction-manual_2205686007.webp)
7
—————— I/O Expansion card ——————
3. Connessione Ingressi-Uscite / Terminal Board
Points
3.1 Connessione Ingressi Digitali / Digital Inputs Terminal
Board Points
Gli ingressi digitali hanno la massa in comune a gruppi di 4.
Connectors XDI0 and XDI1 have different ground connection.
Connector
Terminal
31
32
33
34
35
Function (Fw 1.X ) Digital input 5 Digital input 6 Digital input 7 Digital input 8 GND
Function (Fw 2.X )
DI0X
DI1X
DI2X
DI3X
GND
Connector
Terminal
36
37
38
39
40
Function (Fw 1.X )
n.a.
n.a.
n.a.
n.a.
GND
Function (Fw 2.X )
DI4X
DI5X
DI6X
DI7X
GND
Connector
Terminal
41
42
43
44
45
Function (Fw 1.X )
n.a.
n.a.
n.a.
n.a.
GND
Function (Fw 2.X )
DI8X
DI9X
DI10X
DI11X
GND
n.a. : not available
expDA10
XDI1
XDI0
XDI0
DIGITAL INPUTS
3.2 Connessione Uscite Digitali / Digital Outputs Terminal
Board Points
Le uscite digitali richiedono un’alimentazione esterna di +15V…+24V. Può
essere utilizzata a tale scopo la te24V disponibile in morsettiera del
drive. La massima caricabilità disponibile dal drive a +24V = 120 mA inclusa
l’alimentazione Encoder, LAN, schede EXP e APC (oppure 350mA sono di-
sponibili senza la scheda APC montata).
Al morsetto 60 (PWR) deve essere collegata l’alimentazione positiva, il comune
è il morsetto 55 (COM).
Digital outputs need a +15V…+24V supply voltage. The Drive TB can be used
to supply 24VDC power. AVy 24VDC supply maximum output = 120 mA total
including Encoder, LAN, EXP card and APC (or 350 mA without APC).