gefran 40F 96 Quick Start Manual Download Page 1

105

10

108

96

48

44,5

92

70

115

Triac output (option)

20...240Vac ±10%, 3A max.
Snubberless, inductive and resistive load
I

2

t = 128A

2

S

-1999...9999 (settable decimal point)
Can be converted into engineering units by
inserting a multiplier or divisor (for example, for
display / intercept of rpm)

Scale limits

Faceplate protection

IP65

Working / Storage temperatures

0 to 50°C / -20 to 70°C

Relative humidity

20 to 85%, non-condensing

Installation

Panel mounting, extractable from front

Weight 

320g  for the complete version

Sensor or transducer power supply

5Vdc, 12 Vdc, 120mA max
24 Vdc ± 10%, 50mA max filtered only

Alarms (set points)

Maximum of three configurable alarms:
absolute, deviation, symmetrical deviation.
Adjustable hysteresis

Alarm masking

- exclude on power-up 
- latch reset from key and/or external contact
- insert delay filter (DON, DBI, DOF, DFO)
- set minimum intervention time

Relay contact

NO (NC) 5A, 250V a cos

ϕ

=1

Logic output

type D 11Vdc, Rout = 220

(6V/20mA)

Logic input

Ri = 5,6K

(24V, 4mA), 1500V isolation

Logic input functions

configurable for alarm memory reset, hold, flash,
zero, selection of max., min. peak value, peak-
peak

Analog retransmission (option)

4 to 20mA, max. 150 

load

Fuse (inside device, not
operator serviceable)

100 to 240Vac/dc - type T - 500mA - 250V
11 to 27Vac/dc - type T - 1.25A - 250V

Power supply (switching)

(standard) 100...240Vac/dc ±10% max 11,5VA
(optional) 11...27Vac/dc ±10% max 9VA
50/60Hz

Display

4 digit red LED’s, digit height 14mm

Keys

3 mechanical keys (Raise, Lower, F)

Accuracy

0.1% in autorange mode ± 1 digit with fixed f.s.

Main input

- mechanical contact, no voltage, configurable in

opening/closing, 100Hz filter insertable from
configuration

- from logic control under voltage with amplitude

0.5...30 Vdc, 6 mA max, for proximity PNP or
NPN (inductive or capacitive), encoder or
NAMUR 2 or 3 wires

- maximum frequency of input signal with duty

cycle 50% settable 1, 2, 3, 4, 10, 20, 40, 100 KHz

- from alternate control 30...500V peak, 1 mA max. 
maximum frequency 10KHz
minimum frequency 0.5Hz in sinusoidal mode

For correct and safe
installation, follow the
instructions and observe
the warnings contained
in this manual.

1 • INSTALLATION

• Dimensions and cut-out: Panel mounting

Panel mounting:

Fix the device with the bracket provided before making any electrical connections.
To mount two or more devices side by side, use the cut-out dimensions shown above.

CE MARKINGEMC (electromagnetic compatibility) conformity to EEC Directive
89/336/CEE with reference to the generic Standard EN50082-2 (immunity in industrial
environments) and EN50081-1 (emission in residential environments). BT (low voltage)
conformity to Directive 73/23/CEE as modified by Directive 93/68.
MAINTENANCERepairs must be done out only by trained and specialized personnel.
Cut power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene, etc.).
Use of these solvents can reduce the mechanical reliability of the device. Use a cloth
dampened in ethyl alcohol or water to clean the external plastic case.
SERVICEGEFRAN has a service department. The warranty excludes defects caused
by any use not conforming to these instructions.

2 • TECHNICAL SPECIFICATIONS

FUNCTION

CABLE

LENGTH USED

Input

1 mm

2

3 m

Power supply cable

1 mm

2

1 m

Relay output cables

1 mm

2

3,5 m

EMC conformity has been tested with the following connections

!

40F 96

CONFIGURABLE FREQUENCY INDICATOR - INTERCEPTOR

SOFTWARE VERSION 1.0x 
code 81671B / edition 06 03/08

USER’S MANUAL

Environmental conditions of use

for internal use only, altitude up to 2000m

1

81671B_MHW_40F96_0308_ENG

Summary of Contents for 40F 96

Page 1: ...tude 0 5 30 Vdc 6 mA max for proximity PNP or NPN inductive or capacitive encoder or NAMUR 2 or 3 wires maximum frequency of input signal with duty cycle 50 settable 1 2 3 4 10 20 40 100 KHz from alternate control 30 500V peak 1 mA max maximum frequency 10KHz minimum frequency 0 5Hz in sinusoidal mode For correct and safe installation follow the instructions and observe the warnings contained in t...

Page 2: ...s OUT 1 Alarm 1 OUT 2 Alarm 2 OUT 3 Alarm 3 Label with engineering units Generic user configurable outputs relay 5A 250Vac logic 6V 20mA Rout 220Ω for Out 1 Out 2 Triac 20 240Vac 10 3A max Standard 100 to 240Vac dc 10 Optional 11 to 27Vac dc 10 50 60Hz 8VA max Outputs 12 14 13 15 Out3 Out2 Power supply 11 10 Limit switch 3 wires logic control 4 2 3 1 4 2 3 1 Mechanical contact Limit switch 2 wires...

Page 3: ...resis parameters 999 999 scale points 999 999 scale points Hysteresis for set point 3 Device structure identification of boards F Pressed for approx 2 sec S3 S1 FL1 R20 CPU BOARD POWER SUPPLY BOARD OUTPUT BOARD DISPLAY BOARD Keep the F key pressed to browse the menus Release the F key to enter the displayed menu Press the F key to access the parameters Keep the F key pressed to exit any menu at an...

Page 4: ...ak memory reset 8 Zero peak memory reset 9 Alarms reset 10 Peak alarms reset 11 Zero alarms reset 12 Peak zero alarms reset 13 Output status OUT1 14 Output status OUT2 15 Output status OUT3 Low limit for the alarms set point 1999 9999 High limit for the alarms set point 1999 9999 Minimum scale analog repeat output 1999 9999 Maximum scale analog repeat output 1999 9999 Input parameters 8 enable MU ...

Page 5: ...absolute alarm max with negative H1 1 t 0 For AL2 symmetrical deviation alarm H2 2 t 6 time AL1 AL2 AL1 alarm 1 alarm 2 AL1 AL2 AL1 alarm 1 alarm 2 time AL1 AL2 H2 Normal deviation alarm AL1 absolute AL2 relative Symmetrical deviation alarm AL1 absolute AL2 relative AL1 AL2 AL1 H1 AL1 AL2 H2 AL1 H1 The input value and alarms are frozen while the logic input is active With the logic input active a ...

Page 6: ... DBI Delay in turning on output after output is turned off time time time F 0 3 DOF Delayed deactivation F 0 4 DP0 Delayed activation only at power on Variable rA rA t rA Alarm setpoint Output Alarm Variable rA t rA t rA Alarm setpoint Output Alarm Variable Alarm setpoint Output Alarm Variable rA rA rA rA The diagrams refer to a normal absolute alarm with hysteresis H 0 Filter outputs with referen...

Page 7: ...nding to a full scale of 10KHz is 11 60 Dpe 60 160 12 Ks numerator Ks Ke Dpm 250 80 25 Ks denominator After reducing the function to minimum terms determine MU and dE numerator and denominator P S 3 MU 120 dE 25 EXAMPLE 2 To show the rpms of a wheel with 250 pulses rev with max frequency less than 1 kHz set FP 0 P S 8 full scale 1 KHz MU 6 dE 25 EXAMPLE 3 For applications requiring greater precisi...

Page 8: ...lays thyristor power units particularly if phase angle type motors etc in the same cabinet avoid dust humidity corrosive gases and heat sources do not close the ventilation holes working temperature must be in the range of 0 50 C If the device has faston terminals they must be protected and isolated if the device has screw terminals wires should be attached at least in pairs Power supplied from a ...

Reviews: