User Instructions for GECO GH21TA controller
______________________________________________________________________________
Page 22 Edition I
19.06.2013
In this case, the controller works according to settings communicated by the room panel.
Disconnecting the room panel or damage to the cable connecting the panel to the controller
turns off lights behind the icon
on the screen of the GA03HA room panel.
Follow these steps in order to connect the GH21TA controller to the GA03HA room panel:
Step 1
Step 2
Step 3
Turn off the
driver using the
button
and unplug from
the power supply
→
Connect the
room panel to
the controller
using
connections
58-59-60-61
as shown in the
diagram below
→
Insert the plug
into a 230V
socket and turn
on the controller
using the button
Diagram for connecting the GA03HA room panel to the GH21TA controller
7.5.
Fuel feeder temperature detection
The GH21TA controller has the additional option to protect against temperature in the fuel
feeder tray rising above the permitted level, preventing the flame from heating the fuel.
Fuel feeder temperature detection works in automatic mode the boiler (Automatic,
maintain, alarm). When the temperature measurement exceeds that set in parameter S14, the
fuel feeder activates for the duration set in parameter S16, in order to remove lit fuel from the
feeder. The fan is turned off for the duration of the time set in S16.
When the time set in parameter S15 expires, the controller regains control of the maximum
feeder temperature.