background image

ASSEMBLY OVERVIEW

SETTING

1 Seal cap

2 O-Ring

3 Spring compressor

4 Washer

5 Screws

6 Vent cap

7 Upper cover

8 Plastic Washer

9 Safety diaphragm

10 Calibrated nozzle

11 Washer

12 Disc

13 Compensation diaphragm

14 Upper Bush

15 Disc

16 Working diaphragm

17 Lower bush

18 Cap

19 O-Ring

20 Body

21 Sensing Tube

22 Shaft

23 Seal washer

24 Shaft-Insert Assembly

25 Spring

26 Nut

27 Gasket

28 Cover

29 O-Ring

30 Release button

31 Spring

32 Fitting

33 O-Ring

34 Body

35 O-Ring

36 Reset knob

37 Seeger

38 O-Ring

39 Release shaft

40 Levers assembly

41 Spring

42 Shaft-membrane Assembly

43 O-Ring

44 Insert

45 Cap

46 Screws M4

47 Washer

48 Spring UPSO Min

49 Insert

50 Spring OPSO Max

51 Spring compressor UPSO

52 Spring compressor

53 O-Ring

54 Seal Cap

 Fig.4

2

13

12

16

1

3

4

5

6

7

8

10

11

5

15

20

21

23

27

9

17

22

29

48

51

53

54

45 47

49 50 52

36

37 34

35

32

30

5

28

25

24

19

18

14

26

223mm

238mm

197mm

415mm

DIMENSION

GAS REGULATOR SSV do not require any specific maintenance. Yearly periodi-

cal inspection of regular working 

If necessary, before carrying out any operation with the GAS REGULATOR SSV, 

make sure that  gas supply has been shut off.

Any maintenance operation must be performed by qualified personnel.

MAINTENANCE

50

48

54

52

49

47

51

53

UPSO adjustment screw

Remove to adjust

OPSO adjustment screw

PRESSURE SETTING

Unscrew the 

Seal cap

 

1

 to access to the 

Spring compressor

 

3

 (Fig.4). 

The outlet pressure is regulated by rotating the 

Spring compressor

 (Fig.4). 

Using a 10mm Allen key, turn the 

Spring compressor

 

3

 in a clockwise direction 

to increase the pressure and in an anticlockwise direction to reduce the pressure.

After making the adjustment, replace the 

Seal cap

 

1

.

1" 1/2

4,52

2"

4,4

DIMENSION

WEIGHT (Kgs)

1" 1/4

4,57

Release button

30

MANUAL RESET

Make sure there is pressure inside the system and proceed as follows: 

- Close the tap downstream of the GAS REGULATOR SSV.
- Unscrew and pull down the Reset knob 

36

For pressures over 2 bar, hold the Reset knob down until the pressure balance is 

created inside the system which allows the SSV to be reset (This may also occur 

after several seconds). If this is not the case, it means that the outlet pressure of 

the GAS REGULATOR SSV is lower than the minimum set pressure (UPSO).

RELEASE BUTTON

To stop the gas flow, firmly press the RELEASE button 

30

.

36

REGULATOR GAS SSV

The manufacturer reserves the right make any aesthetic or functional change without notice and at any time.

   dis.8034095    Cod.2.710.XXXX    MADE IN ITALY

GECA

 Srl   

Via E. Fermi, n°98  25064 Gussago (BS) 

Italy Tel. +39 030 3730218  

www.gecasrl.it

Tecnocontrol 

Srl   

Via Miglioli, n°47  20090 Segrate (MI) 

Italy  Tel. +39 02 26922890 

www.tecnocontrol.it

TECHNICAL SPECIFICATIONS

Pmax:

   

inlet max – 500 mbar or 5bar.

Setting outlet

available from 6

 to

 

480mbar - choose the appropriate spring. 

 

 

UPSO

    

available from 5

 to

 

60mbar - choose the appropriate spring.

OPSO

    

available from 150

 to

 

700mbar - choose the appropriate spring.

 

 

Others configuration on request

Inlet - Outlet Connection:

 

 

 

Thread gas 1"1⁄4 , 1"1⁄2 , 2"- ISO 228 connection    

 

 

DN32 DN40 DN50 - Sliding Aluminium flange PN10

Test point

Inlet / outlet on request – Test point 1/8” NPT

Working Temperature: 

- 20 °C ... + 60 °C

Use:

 Not aggressive gases of three families – Natural Gas – LPG –Town Gas

Approval: 

UNI EN 88-1:2008 / PED

MATERIALS:

Complete Body: 

 Die – Cast Aluminium Gd – AlSi12Cu - EN AB 46100

Diaphragms: 

 NBR 60Sh – DvGW EN 549

Plastic components: 

White POM / Pa 66 + 25% Gf

Reviews: