background image

ELECTRICAL CONNECTION

Attention: undertrack cables are required to connect the
instrument to the mains.

The 

Beta

 

752/CO

 gas detector must be powered at 230 Vac using

terminals 1 and 2 (Fig. 3).

INSTALLATION INSTRUCTIONS

Use a screwdriver to undo the screw on the right-hand side of the
instrument and lift the cover (Fig 2).

Position the base correctly and fasten it on the built-in 3-module
box or on the wall, using the screws and dowels provided. Drill
holes in the wall with a 5mm bit for the dowels.

Fig.2

Fig.3

CONNECTING LOADS

There is a JUMPER in the 

Beta 

752/CO

 

 gas detector for selecting

the type of load to be used:

 N.O. position pulse output:

 In the event of an alarm, terminals 8 and 9
 remain closed for 2 seconds every minute
(perfect for normally open electric valves, fig. 5).

N.C. position constant output:

In the event of an alarm, terminals 8 and 9 remain closed
until the alarm stops (perfect for controlling the Normally
Closed  electric  valve  at  the same  time as an external

electric load).

Do not forget that the electric valve must be installed on the gas
pipe outside the room to be controlled as it cannot protect against
leaks upstream.

A circuit breaker must be fitted that is able to disconnect the detector
from the power supply, in accordance with the European standard
IEC EN 60335-1.

CHARACTERISTICS OF THE OUTPUT

The 

Beta 

752/CO

 detector has an output relay with voltage free

contacts; contact rating 8A 250Vac / 30Vdc.

The output consists of a relay with exchange contacts to which any
suitable load can be connected (Fig. 4).

RELAY OUTPU

Fig.4

Fig.5 -Example of jumper with N.O. contact (

PULSE OUTPUT

) and Normally

Open electric valve

.

BETA mod. 752/CO

JUMPER WITH N.O. CONTACT

(PULSE OUTPUT)

In the event of an alarm, it is possible to control any load powered
at 230Vac such as electric extractors, fans, buzzers, etc. (Fig. 5)
using the Normally Open contact of the relay output (terminals 8
and 9).
It is also possible to connect an electric valve which cuts off the
supply of gas in the event of an alarm. A N.O. 230 Vac electric valve
should be connected parallel to the electric load (Fig. 5) while a
N.C. 230 Vac electric valve should be connected using the Normally
Closed contact of the relay (Fig. 6).

GUARANTEE CERTIFICATE

TO COMPILE AND SEND IN CASE OF DAMAGE

DEVICE:      

Beta

 

752/CO

Serial number (s.n.)_________________________________________
DEALER
Stamp:

Date of purchase:
_____/_____/_____

USER
Surname and name _________________________________________
Address _____________________________________ n°__________
Postcode ________________  Town/city ________________________
Telephone_________________________________________________

INSTALLING THE INSTRUMENT

The instrument 

MUST BE INSTALLED

:

- Within easy reach (at a height of about 1.5 m), see Fig. 1.
- At a distance of between 1 and 4 metres from the flame that could
be a possible source of CO.
- If possible, in every room where there is a combustion appliance
(stove, gas boiler, heater with natural draught, etc.).

The instrument 

MUST NOT BE INSTALLED

:

- In corners where there is no free circulation of air.
- Near walls or other obstacles that could prevent the flow of gas
from the flame to the detector, or extractors and fans that could
divert the flow of air.
- In environments where the temperature could exceed 40°C or
fall below – 5°C.
- In environments where there is a high level of humidity or steam.

Fig.1

Installation of the

Beta 752/CO gas

detector

1,5 m

1-4 m

1    2

7    8    9

NC   C    NA

230Vac 50Hz

1

2

230 Vac

 

230V/50Hz 

NA

 

C

 

NC

 

1   2                                 7   8    9            

 

N.O. MANUAL RESET VALVE

Reviews: