3
CONTROL
3.1
Compressor Control Parameters
Control parameters are displayed on the main Omni
Compressor
screen detailed in Section 2.5.1, Page 31.
Below is a list of all control parameters and a brief description of their function.
3.1.1
Capacity Control
The panel supports three sets of capacity parameters. For a user with
Service level
or higher permissions, all
three sets of capacity control parameters will be visible. For a user with
Operator level
permissions, the set dis-
played is dependent on the
Control Mode
parameter detailed in the
Control group
below, and the other two will
be hidden.
Parameter
Units
Minimum
Maximum
Default
Name
Text Entry – See Description
Control Signal
Selection – See Description
Set Point
Dependent on Control Signal. Refer to Panel Data Report
Dead Band
Dependent on Control Signal. Refer to Panel Data Report
Proportional Band
Dependent on Control Signal. Refer to Panel Data Report
Automatic Start/ Stop
Selection – See Description
Automatic Start
Dependent on Control Signal. Refer to Panel Data Report
Automatic Start Offset
Dependent on Control Signal. Refer to Panel Data Report
Automatic Start Delay
Seconds
5 s
1800 s
5 s
Automatic Stop
Dependent on Control Signal. Refer to Panel Data Report
Automatic Stop Offset
Dependent on Control Signal. Refer to Panel Data Report
Automatic Stop Delay
Seconds
5 s
1800 s
5 s
Load Pulse Period
Seconds
1 s
20 s
4 s
Unload Pulse Period
Seconds
1 s
20 s
4 s
Minimum Capacity Slide Position
Percent
0 %
See Description
0 %
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
104
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016