Pause
secs
Pause time between pulses.
Auto stop position
%
As soon as the control slide has reached this value or is below this
value the "Auto stop delay" will start (stand alone operation). In
sequence operation the control slide is stopped at this position and
the compressor is allowed to stop if it is allowed by the sequence
module.
fig.1:
Hysteresis, Neutral Zone
PV
Process value
SP
Setpoint
NZ
Neutral zone
HYS
Hysteresis
A
Time characteristic of process value
B
Time characteristic of the 3-step-controller outputs
C
Time characteristic of the pulse generator
D
Time character of the pulsed outputs to the capacity control solenoid valves
Parameters
Operating Manual | Sequence Control for Packages
GSC TP
10
GEA Refrigeration Germany GmbH | E_301510_2 | Generated 17.12.2014