Compressor assembly
4.7 Operating mode of the lockable service connections
Pipe connection
Pipe connection
Fig. 9
Opening the shut-off valve:
Spindle: turn to the left (counter-clockwise) as far as it will go.
—> Shut-off valve completely opened / service connection closed.
The connection which cannot be shut off is intended for safety devices.
Fig. 10
Opening the service connection
Spindle: Turn ½ - 1 turn to the right clockwise.
—> Service connection opened / shut-off valve opened.
The connection which cannot be shut off is intended for safety devices.
Service connec-
tion closed
Connection
blocked
Spindle
Connection cannot be
shut off
Connection cannot be
shut off
Service connec-
tion opened
Spindle
Connection
open
Compressor
Compressor
After activating the spindle, generally fit the spindle protection cap again and tighten with 14-16 Nm.
This serves as a second sealing feature during operation.
For systems with long pipes and higher degree of contamination, a filter on the suction-side is
recommended. The filter has to be be renewed depending on the degree of contamination (reduced
pressure loss).
4.8 Suction pipe filter