Maintenance
9.5 Decommissioning
Close the shut-off valves on the compressor. Drain the refrigerant (it must not be discharged into the
environment) and dispose of it according to the regulations. When the compressor is depressurised,
undo the fastening screws of the shut-off valves. Remove the compressor using an appropriate hoist.
Dispose of the oil inside in accordance with the applicable national regulations.
9.4 Extract from the lubricants table
The oil type filled as standard in the factory is marked on the
name plate
.
This oil type should be
used as a preference
. Alternatives are stated in the extract from our lubricants table below.
Do not mix oils with each other, use only one type of oil.
Refrigerants
Bock standard oil types
Recommended alternatives
HFC
(e.g. R134a, R407C,
R404A)
Fuchs Reniso Triton SE 55
Fuchs Reniso Triton SEZ 32
Esso/Mobil EAL Arctic 46
Sunoco Suniso SL 46
Texaco Capella HFC 55
HFO
(e.g. R1234yf,
R1234ze, R455A,
R454C))
Fuchs Reniso Triton SE 55
Fuchs Reniso C85E
(from t
O
> 15°C)
---
HCFC
(e.g. R22)
Fuchs Reniso SP 46
Fuchs Reniso SP 32
BP Energol LPT 46
Sunoco Suniso 3,5 GS
Texaco Capella WF 46
HC
(e.g. R290)
Fuchs Synth 68
CPI 1516-68
9.6 Additional information when using flammable refrigerants
WARNING
• During maintenance and repair, it must be noted that hydrocarbon
and synthetic HFO refrigerants residues may dissolve in the
oil. Therefore, electrical tests must not be conducted while oil
remains in the compressor.
• If the compressor is to be removed from the system for
maintenance or repair, the remaining refrigerant must be
suctioned out and the compressor evacuated. The compressor
must then be filled with nitrogen (max. 0.5 bar) and sealed
gas-tight.