background image

49-7415-2

JR 06-01

Air Con

di

ti

o

n

ers

Safety Instructions

 . . . . . . . . . . .2

Operating Instructions

Air Direction  . . . . . . . . . . . . . . . .4
Auxiliary Controls  . . . . . . . . . .5–9
Controls . . . . . . . . . . . . . . . . . . . .3
Vent Control  . . . . . . . . . . . . . . . .4

Care and Cleaning

Air Filters  . . . . . . . . . . . . . . . . . .11
Base Pan  . . . . . . . . . . . . . . . . . .10
Outdoor Coils  . . . . . . . . . . . . . .10
Room Cabinet and Case  . . . . . .10

Installation Instructions

Electrical Supply  . . . . . . . . .14–16
Installing the Zoneline  . . . .17, 18
Optional Drain Kit  . . . . . . . . . .19
Preparation  . . . . . . . . . . . . . . . .12
Replacing an Existing Unit?  . . .13

Troubleshooting Tips

 . . . . . . .20

Normal Operating Sounds  . . . .21

Consumer Support

Consumer Support  . . .Back Cover
Product Registration  . . . . . .25, 26
Warranty  . . . . . . . . . . . . . . . . . .27

Heat/Cool Model 2500

Heat Pump Model 3500

Owner’s Manual and

Installation Instructions

www.GEAppliances.com

Write the model and serial 
numbers here:

Model # ____________________

Serial # ____________________

Find these numbers on a label
behind the room cabinet on the
base pan.

Zoneline

®

Summary of Contents for Zoneline AZ35H09D3B

Page 1: ...Zoneline 17 18 Optional Drain Kit 19 Preparation 12 Replacing an Existing Unit 13 Troubleshooting Tips 20 Normal Operating Sounds 21 Consumer Support Consumer Support Back Cover Product Registration 25 26 Warranty 27 Heat Cool Model 2500 Heat Pump Model 3500 Owner s Manual and Installation Instructions www GEAppliances com Write the model and serial numbers here Model ____________________ Serial _...

Page 2: ...d in accordance with the Installation Instructions before it is used See the Installation Instructions in the back of this manual Immediately repair or replace all electric service cords that have become frayed or otherwise damaged Unplug or disconnect the Zoneline at the fuse box or circuit breaker before making any repairs NOTE We strongly recommend that any servicing be performed by a qualified...

Page 3: ...Series only When the outdoor temperature is lower than 25 F heat is provided by the electric heater in the air conditioner instead of by the heat pump MODE CONTROL TEMP CONTROL STOP LOW FAN HIGH FAN HIGH HEAT HIGH COOL AUTO COOL AUTO HEAT W A R M ER C O O L E R About the controls on your Zoneline www GEAppliances com About Your Heat Pump 3500 Series only Heat pumps can save money by removing heat ...

Page 4: ...y Energy Tip Keep the vent control at CLOSE The room air will be filtered and circulated Air Direction To adjust the air direction remove the room cabinet Remove the 7 louver screws that hold the louver insert in place Flip the louver insert 180 replace the screws and the room cabinet Remove the room cabinet and flip the louver insert to change the air direction 4 Other features your Zoneline may ...

Page 5: ...TL2 H Temp Limit 2 Heat TL3 H Temp Limit 3 Heat TL1 C Temp Limit 1 Cool TL2 C Temp Limit 2 Cool TL3 C Temp Limit 3 Cool Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Customer Service All Electric Heat This electric heat option functions only on the 3500 Series models When this switch is enabled UP heat pump operation is locked out causing the unit to provide onl...

Page 6: ...erface This helps to prevent plumbing damage by turning the heater and indoor fan ON at 41 F and OFF at 46 F Constant ON Fan When this switch is enabled UP it allows the indoor fan to run continuously at high speed even if the unit is in the STOP position Occupancy Sensor When this switch is enabled UP it allows the unit to utilize an infrared motion sensor and a door switch for occupancy detectio...

Page 7: ...5 6 7 8 UP DOWN UP DOWN TL1 C Temp Limit 1 Cool TL2 C Temp Limit 2 Cool TL3 C Temp Limit 3 Cool HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8 UP DOWN UP DOWN TL1 H Temp Limit 1 Heat TL2 H Temp Limit 2 Heat TL3 H Temp Limit 3 Heat Temperature limiting during COOL mode all temperatures shown in F UP DOWN Minimum Maximum NONE 1 2 3 60 85 1 2 3 64 85 1 2 3 66 85 2 1 3 68 85 2 3 1 70 85 1 2 3 NONE 72 85 1 3 2 ...

Page 8: ... the flat of the knob The owner is responsible for making all connections and setting the appropriate dip switches Insert the building hook up wires into the bottom of the terminal and tighten screw securely to make the desired connections CAUTION Improper wiring may damage the Zoneline electronics No common busing is permitted Damage or erratic operation may result A separate wire pair must be ru...

Page 9: ...e wire pair must be run from each separate controlling switch to each individual Zoneline Central Desk Control Remote Thermostat When connected the unit will be controlled by a remote thermostat NOTE The number 4 dip switch must be in the enabled UP position to activate the remote thermostat See the installation instructions supplied with the remote thermostat IMPORTANT The Zoneline thermostat con...

Page 10: ...an if necessary Outdoor Coils The coils on the outdoor side of the Zoneline should be checked regularly If they are clogged with dirt or soot they may be professionally steam cleaned a service available through your GE service outlet You will need to remove the unit to inspect the coils because the dirt build up occurs on the inside Clean the outside coils regularly Room Cabinet and Case Turn the ...

Page 11: ...e air filters Vacuum off the heavy soil Run water through the filters Dry thoroughly before replacing To remove the air filters To replace the air filters CAUTION Do not operate the Zoneline without the filters in place If a filter becomes torn or damaged it should be replaced immediately Operating without the filters in place or with damaged filters will allow dirt and dust to reach the in door c...

Page 12: ...ectrical Code NEC or local codes and ordinances For personal safety this Zoneline must be properly grounded Protective devices fuses or circuit breakers acceptable for Zoneline installations are specified on the nameplate of each unit Do not use an extension cord with this unit Aluminum building wiring may present special problems consult a qualified electrician When the unit is in the STOP positi...

Page 13: ...RAK40 contains air deflectors and gaskets that mount to the unit to direct the hot exhaust air away from the air intake to allow the unit to function properly The grille must have a 65 minimum free area Any vertical deflectors in the existing rear grille should be removed to decrease condenser air recirculation which can cause the unit to short cycle and lead to premature component failure Check t...

Page 14: ...andem 15 Amp 230 208 volt receptacle configuration Perpendicular 20 Amp Large Tandem 30 Amp Order Kit RAK4002A for 230 208 volt direct connection 230 208 volt models may be installed using one of the following electrical subbases Electrical subbases provide a flexible enclosure for direct connection or enclosed receptacles The instructions provided with the selected subbase kit must be carefully f...

Page 15: ... and Proper GE Unit Amperage Rating Subbase Kit 15 RAK204E15 20 RAK204E20 30 RAK204E30 REMOVE JUNCTION BOX 1 Remove the junction box cover by taking out the front two screws 2 Remove the junction box by taking out the top and bottom rear screws Note how the tabs on the lower left side of the junction box serve to hold the side in place This will help when the box is being reinstalled The cord will...

Page 16: ...ew holes at the top and bottom and driving the two screws until secure Be sure that all wire leads are inside the box and not pinched between the box and the unit The identified ribbed Neutral wire of the cordset MUST be connected to the white Neutral wire of the branch circuit The green insulated ground wire from the unit MUST be connected to the branch circuit ground wire 4 265 VOLT ELECTRICAL S...

Page 17: ...ensation from forming on the room side of the case The RAB71 series wall cases are insulated Insulation kit RAK901L is available for use with RAB77 or existing uninsulated wall cases when needed NOTE For installation with a subbase or duct adapter see the instructions packed with those kits 1 Stiffener Protective panel Slit PREPARE THE ROOM CABINET Carefully remove shipping tape if there is any fr...

Page 18: ... into the wall case and secure with four screws through the unit flange holes 3 REPLACE THE ROOM CABINET Reinstall the room cabinet by hooking the top over the rail along the unit top 1 then pushing it in at the bottom 2 4 Installation Instructions 18 ...

Page 19: ...ing onto external building walls we recommend the use of RAD10 Drain Kit External Drain See the Installation Instructions in the RAD10 kit Internal Drain See the Installation Instructions in the RAD10 kit Type A screw for metal case or Type B screw for molded case Square drain holes Square drain holes Neoprene sponge gasket Steel mounting plate 1 2 O D drain tube Neoprene sponge gasket Steel mount...

Page 20: ...r grille must have a minimum of 65 free area Non GE grilles may be too restrictive for proper performance Consult your salesperson for assistance The temp control may Turn the control to a lower or higher setting not be set high enough NOTE The temperature limiter may be limiting the temperature range The air filter is dirty Clean the filter at least every 30 days See the Operating Instructions se...

Page 21: ...ing mode unless the fan switch behind the room cabinet is set at fan cycle up This will cause the fan to cycle on and off with the compressor You may also hear a fan noise stop and start You may notice a few minutes delay in starting if you try to restart the Zoneline too soon after turning it off or if you adjust the thermostat right after the compressor has shut off This is due to a built in res...

Page 22: ...22 Notes Customer Service Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions ...

Page 23: ...Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Customer Service 23 Notes ...

Page 24: ...24 Notes Customer Service Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions ...

Page 25: ...25 General Electric Company Warranty Registration Department P O Box 32150 Louisville KY 40232 2150 Please place in envelope and mail to Cut here ...

Page 26: ...ct is registered or register online at www GEAppliances com 1 2 3 Model Number Serial Number Cut here Complete and mail your Consumer Product Ownership Registration today Have the peace of mind of knowing we can contact you in the unlikely event of a safety modification After mailing the registration below store this document in a safe place It contains information you will need should you require...

Page 27: ...ecessary to move the unit to a location where it is accessible for service by an individual technician Failure or damage resulting from corrosion due to installation in an environment containing corrosive chemicals Replacement of fuses or resetting of circuit breakers Failure of the product resulting from modifications to the product or due to unreasonable use including failure to provide reasonab...

Page 28: ...Website today For the hearing impaired please call 800 TDD GEAC 800 833 4322 Parts and Accessories www GEAppliances com Individuals qualified to service their own appliances can have parts or accessories sent directly to their homes VISA MasterCard and Discover cards are accepted Order on line today 24 hours every day or by phone at 800 626 2002 during normal business hours Instructions contained ...

Reviews: