background image

15

Installation Instructions

265 VOLT ELECTRICAL SUPPLY

WARNING: 

Connection of this 265 V AC product to a branch
circuit 

MUST

be done by direct connection in

accordance with the National Electric Code. 
Plugging this unit into a building mounted 
exposed receptacle is not permitted by code.

These models must be installed using one of the
following methods:

A

Electrical subbase kits are available to provide a
flexible enclosure for direct connection.

The instructions provided with the selected subbase
kit must be carefully followed. It is the responsibility 
of the installer to ensure the connection of
components is done in accordance with these
instructions and all electrical codes.

B

For direct connection to branch circuit wiring inside
the provided junction box without using a subbase 
kit, cut the cord,  strip the wire ends and connect 
as follows.

Branch Circuit and

Proper GE

Unit Amperage Rating

Subbase Kit

15

RAK204E15

20

RAK204E20

30

RAK204E30

REMOVE JUNCTION BOX

1

Remove the junction box cover by taking out the
front two screws.

2

Remove the junction box by taking out the top
and bottom rear screws. Note how the tabs on 
the lower left side of the junction box serve to
hold the side in place. This will help when the 
box is being reinstalled. The cord will be coiled
up inside the junction box.

1

Junction

box cover

Junction box

CUT AND STRIP THE CORDSET

1

Measure 6

down the cord from the strain relief

securing the cord to the unit and cut the cord
through at this point.

2

Carefully split the cord insulation at the center
for 2

so as to separate into three insulated wires.

Be careful not to cut through the center green
ground wire insulation.

3

Strip 3/4

of the insulation away at the end 

of each of the three wires (L1, Neutral and
Ground). The Neutral wire is identified by
molded rib along its entire length. The L1 
(Hot) wire insulation is smooth.

2

Strain

relief

6

2

3/4

Neutral wire

(molded rib)

Ground wire
L1 wire
(smooth)

Summary of Contents for Zoneline 2500

Page 1: ...oneline 17 18 Optional Drain Kit 19 Preparation 12 Replacing an Existing Unit 13 Troubleshooting Tips 20 Normal Operating Sounds 21 Consumer Support Consumer Support Back Cover Product Registration 25...

Page 2: ...in accordance with the Installation Instructions before it is used See the Installation Instructions in the back of this manual Immediately repair or replace all electric service cords that have beco...

Page 3: ...eries only When the outdoor temperature is lower than 25 F heat is provided by the electric heater in the air conditioner instead of by the heat pump MODE CONTROL TEMP CONTROL STOP LOW FAN HIGH FAN HI...

Page 4: ...Energy Tip Keep the vent control at CLOSE The room air will be filtered and circulated Air Direction To adjust the air direction remove the room cabinet Remove the 7 louver screws that hold the louve...

Page 5: ...L2 H Temp Limit 2 Heat TL3 H Temp Limit 3 Heat TL1 C Temp Limit 1 Cool TL2 C Temp Limit 2 Cool TL3 C Temp Limit 3 Cool Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips...

Page 6: ...rface This helps to prevent plumbing damage by turning the heater and indoor fan ON at 41 F and OFF at 46 F Constant ON Fan When this switch is enabled UP it allows the indoor fan to run continuously...

Page 7: ...6 7 8 UP DOWN UP DOWN TL1 C Temp Limit 1 Cool TL2 C Temp Limit 2 Cool TL3 C Temp Limit 3 Cool HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8 UP DOWN UP DOWN TL1 H Temp Limit 1 Heat TL2 H Temp Limit 2 Heat TL3...

Page 8: ...the flat of the knob The owner is responsible for making all connections and setting the appropriate dip switches Insert the building hook up wires into the bottom of the terminal and tighten screw se...

Page 9: ...wire pair must be run from each separate controlling switch to each individual Zoneline Central Desk Control Remote Thermostat When connected the unit will be controlled by a remote thermostat NOTE T...

Page 10: ...n if necessary Outdoor Coils The coils on the outdoor side of the Zoneline should be checked regularly If they are clogged with dirt or soot they may be professionally steam cleaned a service availabl...

Page 11: ...air filters Vacuum off the heavy soil Run water through the filters Dry thoroughly before replacing To remove the air filters To replace the air filters CAUTION Do not operate the Zoneline without th...

Page 12: ...ctrical Code NEC or local codes and ordinances For personal safety this Zoneline must be properly grounded Protective devices fuses or circuit breakers acceptable for Zoneline installations are specif...

Page 13: ...AK40 contains air deflectors and gaskets that mount to the unit to direct the hot exhaust air away from the air intake to allow the unit to function properly The grille must have a 65 minimum free are...

Page 14: ...ndem 15 Amp 230 208 volt receptacle configuration Perpendicular 20 Amp Large Tandem 30 Amp Order Kit RAK4002A for 230 208 volt direct connection 230 208 volt models may be installed using one of the f...

Page 15: ...and Proper GE Unit Amperage Rating Subbase Kit 15 RAK204E15 20 RAK204E20 30 RAK204E30 REMOVE JUNCTION BOX 1 Remove the junction box cover by taking out the front two screws 2 Remove the junction box b...

Page 16: ...w holes at the top and bottom and driving the two screws until secure Be sure that all wire leads are inside the box and not pinched between the box and the unit The identified ribbed Neutral wire of...

Page 17: ...nsation from forming on the room side of the case The RAB71 series wall cases are insulated Insulation kit RAK901L is available for use with RAB77 or existing uninsulated wall cases when needed NOTE F...

Page 18: ...into the wall case and secure with four screws through the unit flange holes 3 REPLACE THE ROOM CABINET Reinstall the room cabinet by hooking the top over the rail along the unit top 1 then pushing it...

Page 19: ...ng onto external building walls we recommend the use of RAD10 Drain Kit External Drain See the Installation Instructions in the RAD10 kit Internal Drain See the Installation Instructions in the RAD10...

Page 20: ...grille must have a minimum of 65 free area Non GE grilles may be too restrictive for proper performance Consult your salesperson for assistance The temp control may Turn the control to a lower or hig...

Page 21: ...ng mode unless the fan switch behind the room cabinet is set at fan cycle up This will cause the fan to cycle on and off with the compressor You may also hear a fan noise stop and start You may notice...

Page 22: ...22 Notes Customer Service Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions...

Page 23: ...Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Customer Service 23 Notes...

Page 24: ...24 Notes Customer Service Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions...

Page 25: ...25 General Electric Company Warranty Registration Department P O Box 32150 Louisville KY 40232 2150 Please place in envelope and mail to Cut here...

Page 26: ...t is registered or register online at www GEAppliances com 1 2 3 Model Number Serial Number Cut here Complete and mail your Consumer Product Ownership Registration today Have the peace of mind of know...

Page 27: ...cessary to move the unit to a location where it is accessible for service by an individual technician Failure or damage resulting from corrosion due to installation in an environment containing corros...

Page 28: ...ebsite today For the hearing impaired please call 800 TDD GEAC 800 833 4322 Parts and Accessories www GEAppliances com Individuals qualified to service their own appliances can have parts or accessori...

Reviews: