1-4
VersaMax PROFINET Scanner Manual
– December 2013
GFK-2721A
1
VersaMax PROFINET Scanner Specifications
PROFINET Support
PROFINET Version 2.3 Class A IO-Device
Redundantly controlled operation conforms to PROFINET V2.3 Type S-2
System Redundancy.
RX3i CPU Version
Required
Firmware version 8.00 or later
RX3i PNC Version
Required
2.00 or later
Proficy Machine Edition
Version Required
Version 8.0 or later
Power Consumption
IC200PNS001: 0.60A at 5VDC
IC200PNS002: 1.10A at 5VDC
Module Dimensions
Height: 132mm (5.2 inches), Width: 134mm (5.28 inches)
Carrier Required
No. Carrier is integrated into the module.
Operating Temperature
Range
0 to 60°C surrounding air temperature without a fan
Number of Port
Connectors
IC200PNS001: Two RJ-45
IC200PNS002: Two SC-Duplex
USB Connector
(for
firmware upgrades)
One Micro-B connector. USB 2.0 compliant running at Full-speed
(12 MHz)
PNS Status and Control
Bits
32 input status bits and 32 output control bits
I/O Data Update on the
PROFINET network
Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms
and 512ms
Number of IP addresses
One. Supports Classless Inter-Domain Routing (CIDR)
Number of MAC
Addresses
Three. One per external port and one internal. External MAC addresses
are only used for specialized Ethernet protocols such as MRP or LLDP
I/O Station Maximum
Limits
Number of I/O Modules per
station
8
I/O data per station
2880 bytes total
1440 bytes of input data
1440 bytes of output data
RoHS Compliance
Yes
Configuration
Configured using Proficy Machine Edition when used with a
PACSystems RX3i PROFINET Controller (PNC) module, as part
of an RX3i PROFINET network.
V2.3 GSDML file is available for import into 3
rd
-Party tools.
For product standards, general operating specifications, and installation requirements, refer to
the
VersaMax I/O Modules Manual
, GFK-1504.