GE Multilin
T60 Transformer Protection System
2-1
2 PRODUCT DESCRIPTION
2.1 INTRODUCTION
2
2 PRODUCT DESCRIPTION 2.1INTRODUCTION
2.1.1 OVERVIEW
The T60 Transformer Protection System is a microprocessor-based relay for protection of small, medium, and large three-
phase power transformers. The relay can be configured with a maximum of four three-phase current inputs and four ground
current inputs, and can satisfy applications with transformer windings connected between two breakers, such as in a ring
bus or in breaker-and-a-half configurations. The T60 performs magnitude and phase shift compensation internally, eliminat-
ing requirements for external CT connections and auxiliary CTs.
The percent differential element is the main protection device in the T60. Instantaneous differential protection, volts-per-
hertz, restricted ground fault, and many current, voltage, and frequency-based protection elements are also incorporated.
The T60 includes sixteen fully programmable universal comparators, or FlexElements™, that provide additional flexibility
by allowing the user to customize their own protection functions that respond to any signals measured or calculated by the
relay.
The metering functions of the T60 include true RMS and phasors for currents and voltages, current harmonics and THD,
symmetrical components, frequency, power, power factor, and energy.
Diagnostic features include an event recorder capable of storing 1024 time-tagged events, oscillography capable of storing
up to 64 records with programmable trigger, content and sampling rate, and data logger acquisition of up to 16 channels,
with programmable content and sampling rate. The internal clock used for time-tagging can be synchronized with an IRIG-
B signal or via the SNTP protocol over the Ethernet port. This precise time stamping allows the sequence of events to be
determined throughout the system. Events can also be programmed (via FlexLogic™ equations) to trigger oscillography
data capture which may be set to record the measured parameters before and after the event for viewing on a personal
computer (PC). These tools significantly reduce troubleshooting time and simplify report generation in the event of a sys-
tem fault.
A faceplate RS232 port may be used to connect to a PC for the programming of settings and the monitoring of actual val-
ues. A variety of communications modules are available. Two rear RS485 ports allow independent access by operating and
engineering staff. All serial ports use the Modbus
®
RTU protocol. The RS485 ports may be connected to system computers
with baud rates up to 115.2 kbps. The RS232 port has a fixed baud rate of 19.2 kbps. Optional communications modules
include a 10/100Base-F Ethernet interface which can be used to provide fast, reliable communications in noisy environ-
ments. Another option provides two 10/100Base-F fiber optic ports for redundancy. The Ethernet port supports IEC 61850,
Modbus
®
/TCP, and TFTP protocols, and allows access to the relay via any standard web browser (T60 web pages). The
IEC 60870-5-104 protocol is supported on the Ethernet port. DNP 3.0 and IEC 60870-5-104 cannot be enabled at the same
time.
Settings and actual values can be accessed from the front panel or EnerVista software.
The T60 IEDs use flash memory technology that allows field upgrading as new features are added.
The following
Single line diagram
illustrates the relay functionality using ANSI (American National Standards Institute)
device numbers.
Table 2–1: ANSI DEVICE NUMBERS AND FUNCTIONS
DEVICE
NUMBER
FUNCTION
DEVICE
NUMBER
FUNCTION
21G
Ground distance
51N
Neutral time overcurrent
21P
Phase distance
51P
Phase time overcurrent
24
Volts per hertz
59N
Neutral overvoltage
25
Synchrocheck (optional)
59P
Phase overvoltage
27P
Phase undervoltage
59X
Auxiliary overvoltage
27X
Auxiliary undervoltage
67N
Neutral directional overcurrent
49
Thermal overload protection
67P
Phase directional overcurrent
50/87
Instantaneous differential overcurrent
68
Power swing blocking
50BF
Breaker failure
78
Out-of-step tripping
50G
Ground instantaneous overcurrent
81O
Overfrequency
50N
Neutral instantaneous overcurrent
81U
Underfrequency
50P
Phase instantaneous overcurrent
87G
Restricted ground fault
51G
Ground time overcurrent
87T
Transformer differential
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...