2-56
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
4501
Phase VT 1 Secondary
25 to 240
V
0.1
F001
664
"
4502
Phase VT 1 Ratio
1 to 24000
:1
1
F060
1
"
4504
Auxiliary VT 1 Connection
0 to 6
---
1
F166
1 (Vag)
"
4505
Auxiliary VT 1 Secondary
25 to 240
V
0.1
F001
664
"
4506
Auxiliary VT 1 Ratio
1 to 24000
:1
1
F060
1
"
4508
...Repeated for VT Bank 2
"
4510
...Repeated for VT Bank 3
"
4518
...Repeated for VT Bank 4
"
4520
...Repeated for VT Bank 5
"
4528
...Repeated for VT Bank 6
Source Settings (Read/Write Setting) (2, 4, or 6 Modules)
All except B90,
C30
4580
Source 1 Name
0 to 1
---
1
F206
“SRC 1"
"
4583
Source 1 Phase CT
0 to 63
---
1
F400
0
"
4584
Source 1 Ground CT
0 to 63
---
1
F400
0
"
4585
Source 1 Phase VT
0 to 63
---
1
F400
0
"
4586
Source 1 Auxiliary VT
0 to 63
---
1
F400
0
"
4587
...Repeated for Source 2
B30, C60, C70,
D60, F35, F60,
G30, G60, L60,
L90, M60, N60,
T35, T60
458E
...Repeated for Source 3
"
4595
...Repeated for Source 4
B30, C70, F35,
N60, T35, T60
459C
...Repeated for Source 5
"
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
All except B90,
C30
4600
Nominal Frequency
25 to 60
Hz
1
F001
60
"
4601
Phase Rotation
0 to 1
---
1
F106
0 (ABC)
"
4602
Frequency and Phase Reference
0 to 5
---
1
F167
0 (SRC 1)
"
4603
Frequency Tracking Function
0 to 1
---
1
F102
1 (Enabled)
Change Phase Rotation (Read/Write Setting)
G30, G60
4604
Change Phase Rotation
0 to 4294967295
---
1
F300
0
87L Power System In-Zone Transformer (Read/Write Setting)
L30, L90
4606
In-Zone Transformer Connection
0 to 12
---
1
F560
0 (None)
"
4607
87L In-Zone Transformer Location
0 to 2
---
1
F562
0 (Local-Tap)
Power System (Read/Write Setting)
L90
4610
Number of Terminals
2 to 3
---
1
F001
2
"
4611
Number of Channels
1 to 2
---
1
F001
1
"
4612
Charging Current Compensation
0 to 1
---
1
F102
0 (Disabled)
"
4613
Positive Sequence Reactance
0.1 to 65.535
kohms
0.001 F001
100
"
4614
Zero Sequence Reactance
0.1 to 65.535
kohms
0.001 F001
100
"
4615
Zero Sequence Current Removal
0 to 1
---
1
F102
0 (Disabled)
"
4616
Local Relay ID
0 to 255
---
1
F001
0
"
4617
Terminal 1 ID
0 to 255
---
1
F001
0
"
4618
Terminal 2 ID
0 to 255
---
1
F001
0
"
4619
Channel Asymmetry Compensation
0 to 4294967295
---
1
F300
0
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...