B-30
L60 Line Phase Comparison System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
60E3
Breaker 2 Auxiliary Contact
0 to 65535
---
1
F300
0
60E4
Breaker 2 Supervision Element
0 to 65535
---
1
F300
0
60E5
Weak-Infeed Keying
0 to 65535
---
1
F300
0
60E6
Supervision Element
0 to 65535
---
1
F300
0
60E7
Infeed Pickup Delay
0 to 50
s
0.001
F001
0
60E8
Infeed Reset Delay
0 to 50
s
0.001
F001
35
60E9
Open Breaker Keying Pickup Delay
0 to 50
s
0.001
F001
0
60EA
Open Breaker Keying Reset Delay
0 to 50
s
0.001
F001
0
Phase Comparison Trip Scheme (Read/Write Grouped Setting)
60F0
87PC Function
0 to 1
---
1
F102
0 (Disabled)
60F1
87PC Channel Loss
0 to 500
ms
0.001
F001
0
60F2
87PC Block
0 to 65535
---
1
F300
0
60F3
87PC Target
0 to 2
---
1
F109
0 (Self-reset)
60F4
87PC Events
0 to 1
---
1
F102
0 (Disabled)
60F5
87PC Scheme Select
0 to 8
---
1
F149
1 (2TL-BL-DPC-3FC)
60F6
87PC Scheme Signal
0 to 1
---
1
F150
0 (MIXED I_2 - K*I_1)
60F7
87PC Signal Source
0 to 5
---
1
F167
0 (SRC 1)
60F8
87PC FDL Pickup
0.01 to 15
pu
0.01
F001
50
60FA
87PC FDH Pickup
0.01 to 15
pu
0.01
F001
75
60FB
87PC Mixed Signal K
0 to 0.25
---
0.01
F001
20
60FE
87PC Phase Delay Ch1
0 to 65.535
ms
0.001
F003
0
6100
87PC Phase Delay Ch2
0 to 65.535
ms
0.001
F003
0
6106
87PC Transient Pickup
0 to 65.535
s
0.001
F003
30
610A
87PC Asymmetry Channel 1
–20 to 20
ms
0.1
F004
0
610E
87PC Asymmetry Channel 2
–20 to 20
ms
0.1
F004
0
6110
87PC Stability Angle
40 to 140
degrees
10
F003
75
6112
87PC Transient Reset
0 to 65.535
s
0.001
F003
30
6113
87PC Received Volts Channel 1
0 to 125
V
0.1
F001
120
6114
87PC Received Volts Channel 2
0 to 125
V
0.1
F001
120
6115
87PC High-Speed Contact 1
0 to 64
---
1
F490
0
6116
87PC High-Speed Contact 2
0 to 64
---
1
F490
0
6117
87PC FDL AUX
0 to 65535
---
1
F300
0
6118
87PC FDH AUX
0 to 65535
---
1
F300
0
6119
87PC Reset Delay
0 to 200
ms
1
F001
30
611A
87PC Mixed Signal Reference Angle
0 to 359
°
1
F001
0
611B
87PC Trip Security
0 to 1
---
1
F534
0 (First Coincidence)
611C
87PC Second Coincidence Timer
10 to 200
ms
1
F001
40
611D
87PC Enhanced Stability Angle
40 to 180
°
5
F001
110
611E
87PC FDH Supervision
0 to 65535
---
1
F300
0
611F
87PC Pickup Delay
0 to 50
ms
1
F001
0
6120
87PC Stop Tx
0 to 65535
---
1
F300
0
6121
87PC Tx Reset Delay
0 to 1000
ms
1
F001
0
CT Failure Detector (Read/Write Setting)
6124
CT Fail Function
0 to 1
---
1
F102
0 (Disabled)
6125
CT Fail Block
0 to 65535
---
1
F300
0
6126
CT Fail Current Source 1
0 to 5
---
1
F167
0 (SRC 1)
6127
CT Fail Current Pickup 1
0 to 2
pu
0.1
F001
2
6128
CT Fail Current Source 2
0 to 5
---
1
F167
1 (SRC 2)
6129
CT Fail Current Pickup 2
0 to 2
pu
0.1
F001
2
612A
CT Fail Voltage Source
0 to 5
---
1
F167
0 (SRC 1)
612B
CT Fail Voltage Pickup
0 to 2
pu
0.01
F001
20
612C
CT Fail Pickup Delay
0 to 65.535
s
0.001
F001
1000
612D
CT Fail Target
0 to 2
---
1
F109
0 (Self-reset)
612E
CT Fail Events
0 to 1
---
1
F102
0 (Disabled)
Table B–9: MODBUS MEMORY MAP (Sheet 22 of 55)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...