GE Multilin
L60 Line Phase Comparison System
2-9
2 PRODUCT DESCRIPTION
2.2 SPECIFICATIONS
2
2.2SPECIFICATIONS
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
2.2.1 PROTECTION ELEMENTS
The operating times below include the activation time of a trip rated form-A output contact unless otherwise indi-
cated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
interfacing with other IEDs or power system devices via communications or different output contacts.
87PC SCHEME
Signal selection:
mixed I_2 –
K
× I_1 (
K
= 0.00 to 0.25 in
steps of 0.01), or 3I_0
Angle reference:
0 to 360° leading in steps of 1
Fault detector low:
Mixed signal overcurrent: 0.02 to 15.00 pu in steps of 0.01
I
2
×
Z
–
V
2
:
0.005 to 15.000 pu in steps of 0.001
d
I
2
/ d
t
:
0.01 to 5.00 pu in steps of 0.01
d
I
1
/ d
t
:
0.01 to 5.00 pu in steps of 0.01
I
1
overcurrent:
0.20 to 5.00 pu in steps of 0.01
I
2
overcurrent:
0.02 to 5.00 pu in steps of 0.01
Fault detector high:
Mixed signal overcurrent: 0.10 to 15.00 pu in steps of 0.01
I
2
×
Z
–
V
2
:
0.005 to 15.000 pu in steps of 0.001
d
I
2
/ d
t
:
0.01 to 5.00 pu in steps of 0.01
d
I
1
/ d
t
:
0.01 to 5.00 pu in steps of 0.01
I
1
overcurrent:
0.50 to 5.00 pu in steps of 0.01
I
2
overcurrent:
0.05 to 5.00 pu in steps of 0.01
Signal symmetry
adjustment:
–5.0 to 5.0 ms in steps of 0.1
Channel delay
adjustment:
0.000 to 30.00 ms in steps of 0.001
Channel adjustments:
channel delay and signal symmetry com-
pensation
Operate time (typical):
¾ cycle for single phase comparison
½ cycle for dual phase comparison
Trip security:
first coincidence or enhanced
Second coincidence timer: 10 to 200 ms in steps of 1
Enhanced stability angle: 40 to 180° in steps of 1
Charging current compensation: 0.100 to 65.535 k
Ω
in steps of
0.001
PHASE DISTANCE
Characteristic:
mho (memory polarized or offset) or
quad (memory polarized or non-direc-
tional), selectable individually per zone
Number of zones:
3
Directionality:
forward, reverse, or non-directional
Reach (secondary
Ω
):
0.02 to 500.00
Ω
in steps of 0.01
Reach accuracy:
±5% including the effect of CVT tran-
sients up to an SIR of 30
Distance:
Characteristic angle:
30 to 90° in steps of 1
Comparator limit angle: 30 to 90° in steps of 1
Directional supervision:
Characteristic angle:
30 to 90° in steps of 1
Limit angle:
30 to 90° in steps of 1
Right blinder (Quad only):
Reach:
0.02 to 500
Ω
in steps of 0.01
Characteristic angle:
60 to 90° in steps of 1
Left Blinder (Quad only):
Reach:
0.02 to 500
Ω
in steps of 0.01
Characteristic angle:
60 to 90° in steps of 1
Time delay:
0.000 to 65.535 s in steps of 0.001
Timing accuracy:
±3% or 4 ms, whichever is greater
Current supervision:
Level:
line-to-line current
Pickup:
0.050 to 30.000 pu in steps of 0.001
Dropout:
97 to 98%
Memory duration:
5 to 25 cycles in steps of 1
VT location:
all delta-wye and wye-delta transformers
CT location:
all delta-wye and wye-delta transformers
Voltage supervision pickup (series compensation applications):
0 to 5.000 pu in steps of 0.001
Operation time:
1 to 1.5 cycles (typical)
Reset time:
1 power cycle (typical)
NOTE
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...