GE Multilin
L60 Line Phase Comparison System
5-157
5 SETTINGS
5.5 GROUPED ELEMENTS
5
IEC CURVES
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142. These
are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The formulae for these curves are:
,
(EQ 5.11)
where:
T
= operate time (in seconds),
TDM
= Multiplier setting,
I
= input current,
I
pickup
= Pickup Current setting,
K
,
E
=
constants,
t
r
= characteristic constant, and
T
RESET
= reset time in seconds (assuming energy capacity is 100%
and
RESET
is “Timed”)
Table 5–17: IEC (BS) INVERSE TIME CURVE CONSTANTS
IEC (BS) CURVE SHAPE
K
E
T
R
IEC Curve A (BS142)
0.140
0.020
9.7
IEC Curve B (BS142)
13.500
1.000
43.2
IEC Curve C (BS142)
80.000
2.000
58.2
IEC Short Inverse
0.050
0.040
0.500
Table 5–18: IEC CURVE TRIP TIMES (IN SECONDS)
MULTIPLIER
(TDM)
CURRENT ( I / I
pickup
)
1.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
IEC CURVE A
0.05
0.860
0.501
0.315
0.249
0.214
0.192
0.176
0.165
0.156
0.149
0.10
1.719
1.003
0.630
0.498
0.428
0.384
0.353
0.330
0.312
0.297
0.20
3.439
2.006
1.260
0.996
0.856
0.767
0.706
0.659
0.623
0.594
0.40
6.878
4.012
2.521
1.992
1.712
1.535
1.411
1.319
1.247
1.188
0.60
10.317
6.017
3.781
2.988
2.568
2.302
2.117
1.978
1.870
1.782
0.80
13.755
8.023
5.042
3.984
3.424
3.070
2.822
2.637
2.493
2.376
1.00
17.194
10.029
6.302
4.980
4.280
3.837
3.528
3.297
3.116
2.971
IEC CURVE B
0.05
1.350
0.675
0.338
0.225
0.169
0.135
0.113
0.096
0.084
0.075
0.10
2.700
1.350
0.675
0.450
0.338
0.270
0.225
0.193
0.169
0.150
0.20
5.400
2.700
1.350
0.900
0.675
0.540
0.450
0.386
0.338
0.300
0.40
10.800
5.400
2.700
1.800
1.350
1.080
0.900
0.771
0.675
0.600
0.60
16.200
8.100
4.050
2.700
2.025
1.620
1.350
1.157
1.013
0.900
0.80
21.600
10.800
5.400
3.600
2.700
2.160
1.800
1.543
1.350
1.200
1.00
27.000
13.500
6.750
4.500
3.375
2.700
2.250
1.929
1.688
1.500
IEC CURVE C
0.05
3.200
1.333
0.500
0.267
0.167
0.114
0.083
0.063
0.050
0.040
0.10
6.400
2.667
1.000
0.533
0.333
0.229
0.167
0.127
0.100
0.081
0.20
12.800
5.333
2.000
1.067
0.667
0.457
0.333
0.254
0.200
0.162
0.40
25.600
10.667
4.000
2.133
1.333
0.914
0.667
0.508
0.400
0.323
0.60
38.400
16.000
6.000
3.200
2.000
1.371
1.000
0.762
0.600
0.485
0.80
51.200
21.333
8.000
4.267
2.667
1.829
1.333
1.016
0.800
0.646
1.00
64.000
26.667
10.000
5.333
3.333
2.286
1.667
1.270
1.000
0.808
IEC SHORT TIME
0.05
0.153
0.089
0.056
0.044
0.038
0.034
0.031
0.029
0.027
0.026
0.10
0.306
0.178
0.111
0.088
0.075
0.067
0.062
0.058
0.054
0.052
0.20
0.612
0.356
0.223
0.175
0.150
0.135
0.124
0.115
0.109
0.104
0.40
1.223
0.711
0.445
0.351
0.301
0.269
0.247
0.231
0.218
0.207
0.60
1.835
1.067
0.668
0.526
0.451
0.404
0.371
0.346
0.327
0.311
0.80
2.446
1.423
0.890
0.702
0.602
0.538
0.494
0.461
0.435
0.415
1.00
3.058
1.778
1.113
0.877
0.752
0.673
0.618
0.576
0.544
0.518
T
TDM
K
I I
pickup
⁄
(
)
E
1
–
---------------------------------------
×
=
T
RESET
TDM
t
r
1
I I
pickup
⁄
(
)
2
–
---------------------------------------
×
=
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...