5-106
C70 Capacitor Bank Protection and Control System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
5.6.3 BREAKER FAILURE
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
BREAKER FAILURE
Ö
BREAKER FAILURE 1
BREAKER FAILURE 1
BF1 FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
BF1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
MESSAGE
BF1 SOURCE:
SRC 1
Range: SRC 1, SRC 2
MESSAGE
BF1 USE AMP SUPV:
Yes
Range: Yes, No
MESSAGE
BF1 USE SEAL-IN:
Yes
Range: Yes, No
MESSAGE
BF1 3-POLE INITIATE:
Off
Range: FlexLogic™ operand
MESSAGE
BF1 BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
BF1 PH AMP SUPV
PICKUP: 1.050 pu
Range: 0.001 to 30.000 pu in steps of 0.001
MESSAGE
BF1 N AMP SUPV
PICKUP: 1.050 pu
Range: 0.001 to 30.000 pu in steps of 0.001
MESSAGE
BF1 USE TIMER 1:
Yes
Range: Yes, No
MESSAGE
BF1 TIMER 1 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BF1 USE TIMER 2:
Yes
Range: Yes, No
MESSAGE
BF1 TIMER 2 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BF1 USE TIMER 3:
Yes
Range: Yes, No
MESSAGE
BF1 TIMER 3 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BF1 BKR POS1
φ
A/3P:
Off
Range: FlexLogic™ operand
MESSAGE
BF1 BKR POS2
φ
A/3P:
Off
Range: FlexLogic™ operand
MESSAGE
BF1 BREAKER TEST ON:
Off
Range: FlexLogic™ operand
MESSAGE
BF1 PH AMP HISET
PICKUP: 1.050 pu
Range: 0.001 to 30.000 pu in steps of 0.001
MESSAGE
BF1 N AMP HISET
PICKUP: 1.050 pu
Range: 0.001 to 30.000 pu in steps of 0.001
MESSAGE
BF1 PH AMP LOSET
PICKUP: 1.050 pu
Range: 0.001 to 30.000 pu in steps of 0.001