TVRMS2 Digital Test Kit
Chapter 5. MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units
15
5–1 Test Structure (MicroVersaTrip
Plus™ and MicroVersaTrip PM™)
Figure 11 shows the test-selection structure for Micro-
VersaTrip Plus and MicroVersaTrip PM Trip Units. Each
test sequence is described in detail below.
If an A, B, C, or TT Trip Unit or Spectra breaker is
selected, the Test Kit immediately displays the main test-
selection menu:
... ..... ..... ..
Press F1,F2, or F3 for test selection
|FUNCTION |HICURRENT| QUICK |
Main test-selection menu.
With some versions of A, B, or C type Trip Units, the Test
Kit displays the following menu:
... ..... .....
Is the GF option included?
|- YES -| |- NO -|– EXIT –|
Ground Fault option query menu.
If the Ground Fault option is included in the Trip Unit,
press
YES
(
F1
). Otherwise, press
NO
(
F3
) to go to the main
test selection menu. Press
EXIT
(
F4
) at any time to return
to the Trip Unit selection menu.
Selecting
FUNCTION
(
F1
)
from the main test-selection
menu displays the Trip Units tests menu:
.
.
.
..
. .
.
.
. .
.. .. .
. ..... ..
. .
...
Press F1 or F3 (F4 to EXIT)
|TRIP TEST| |SELF TEST|– EXIT –|
Trip Units tests menu.
Trip Test mode is described in section
5-3 Overcurrent
Simulation
and Self-Test is described in section
5-2 Self-Test
Report
. Press
EXIT
(
F4
) to return to the function test menu.
Test Selection
High-Current
Tests
Quick
Test
Function
Tests
Trip
Breaker
GF Defeat
and Monitor
Self-
Tests
Overcurrent
Tests
Trip
Tests
No-Trip
Tests
LT
ST
GF
LT
ST
GF
Trip Unit
Status Report
Enter Settings
LT
ST
GF
Figure 11. Test-selection structure for MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units.