NSTALLATION REQUIREMENTS 

(

CONT

.):

 

system.   Refer to the 

VOLTAGE RATINGS & POWER SOURCE 

CONFIGURATIONS” chart below.  The TVSS model number can be found on the 
front of the unit.

 

 

Verify that an NEC (National Electrical Code) compliant X0 bond has been made at 
the upstream transformer that feeds the electrical supply panel.  Per NEC 250.30, this 
bond must be in place on all grounded electrical systems.   

 

The TR5451 or TR5452 model TVSS must be installed on a dedicated branch circuit 
breaker.  The maximum allowable rating for the circuit breaker is 30A / 22kAIC.

 

 

 

Do not attempt to install the TVSS on the upstream (line) side of the Main Breaker or 
Fuse.   

 

The TVSS should only be installed indoors in NEMA 1 type locations.  Do not install 
the TVSS outside or in wet locations.

 

Single Phase

2 Wire + Ground

150V  (L-N / L-G)

270V  (L-N / L-G)

120V

240V

ACT451-120

ACT 451-240

Split Phase

3 Wire + Ground

150V  (L-N / L-G)

270V  (L-N / L-G)

120 / 240V

240 / 480V

ACT452-120

ACT452-240

SOURCE 

CONFIGURATION

SYSTEM

TYPE

MAXIMUM 

CONTINOUS RMS 

OPERATING 

VOLTAGE

NOMINAL

VOLTAGE

(50/60hZ)

MODEL

TYPE

L1

L2

N

VOLTAGE RATINGS & POWER SOURCE CONFIGURATIONS

L1

N

 

 

I

NSTALLATION

 

POWER MUST BE PROVEN DISCONNECTED BEFORE 
STARTING INSTALLATION, INSPECTION OR MAINTENANCE!  
FAILURE TO DO SO MAY CAUSE SERIOUS INJURY, DEATH 
AND/OR PROPERTY DAMAGE

.   

Before attempting installation, make sure that the pre-
installation requirements of this manual have been satisfied.  
If the status of the pre-installation requirements are not 
known, do not attempt to continue.  

M

OUNTING

 

 

1. 

  TR5451 and TR5452 TVSS units are designed to be 

mounted directly to the electrical panel through a ½” 
knockout.  Mounting feet are also supplied for instances 
where direct connection to the panel is not practical.  Select 
a location that will allow the closest proximity to the breaker 
that the TVSS will be connected to.  

2. 

Use the ½” threaded fitting and spacer to secure the 

TVSS to the Electrical Panel that is to be protected. 

 

903-640-0555
800-950-2281

NOTE:  If lamp is out, replace unit

LISTED (48E6)

UL 1449, 2

ND

EDITION

FOR INDOOR USE ONLY

 

DUAL PHASE TVSS

120 VAC 50/60HZ

SUPPRESSION VOLTAGES

330 L-N
600 L-L

TVSS
PART# ACT452120210N
DATE CODE:     WO#

Electrical 
Panel 

Spacer 

Threaded 
Fitting 

ACT452-120 

120V 

150V  (L-N / L-G)

TR5451-120 
 
 
 
TR5451-240

 

 
 
TR5452-120

 

Summary of Contents for TR5451

Page 1: ...to ensure that the proper TVSS model number has been selected for your SPECIAL ATTENTION MUST BE GIVEN TO VERIFY THAT A PROPER NEUTRAL GROUND XO BOND HAS BEEN MADE WHEN POWER IS SUPPLIED FROM AN UPSTREAM TRANSFORMER OR ANY OTHER TYPE OF SEPARATELY DERIVED POWER SOURCE FAILURE TO PROVIDE THIS BOND AS REQUIRED PER ARTICLE 250 30 OF THE NATIONAL ELECTRICAL CODE CAN RESULT IN ELEVATED PHASE TO GROUND ...

Page 2: ...OLTAGE NOMINAL VOLTAGE 50 60hZ MODEL TYPE L1 L2 N VOLTAGE RATINGS POWER SOURCE CONFIGURATIONS L1 N INSTALLATION POWER MUST BE PROVEN DISCONNECTED BEFORE STARTING INSTALLATION INSPECTION OR MAINTENANCE FAILURE TO DO SO MAY CAUSE SERIOUS INJURY DEATH AND OR PROPERTY DAMAGE Before attempting installation make sure that the pre installation requirements of this manual have been satisfied If the status...

Page 3: ...ground terminal of the TVSS This feature should only be utilized for OEM installations where this type of configuration has been evaluated as suitable For all other installations the jumpers should be removed so that the alarm contacts will function normally per paragraph 3 above OPERATION 1 When energized the green LED status indicator lamps located on the front of the TVSS will be illuminated Fo...

Page 4: ...ieved the published design specifications A certificate of compliance is available upon request NOTICE These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered suffic...

Reviews: