GEK-98834B
8
$X[LOLDU\&RQWDFWV&DSDFLW\
Continuous:
3 A
Make and carry:
5 A during 30 s.
Break:
25 W inductive at 125/250 VDC
Carry continuously: 20 W maximum of 250 VDC or 5 A.
$FFXUDF\
Voltage:
±
5%
Time:
±
5% or 30 ms (whichever is greater).
$XPLGLW\
Up to 95% without condensation.
)UHTXHQF\5DQJH
SINGLE PHASE
THREE PHASE
Rated frequency
50 or 60 Hz
50/60 Hz
Effective range
48/51 Hz or 57/63 Hz
48/63 Hz
Operative range
46/53 Hz or 56/64 Hz
46/64 Hz
%XUGHQV
20-275 VAC and 50-305 VAC ranges
3-66 VAC range
Tap set to 50 VAC
Tap set to 5 VAC
V (VAC)
VA
V(VAC)
VA
30
0.012
5
0.019
120
0.100
25
0.022
210
0.291
45
0.053
300
0.783
65
0.092
0D[LPXP9ROWDJH
Ranges 20-275 VAC and 50-305 VAC:
400 VAC continuously.
Range 3-66 VAC
200 VAC Continuously.