GE Multilin
T60 Transformer Protection System
6-25
6 ACTUAL VALUES
6.3 METERING
6
The above actual values are displayed without the corresponding time stamp as they become available per the recording
rate setting. Also, the recording post-filtering setting is applied to these values.
6.3.10 PMU AGGREGATOR
PATH: ACTUAL VALUES
METERING
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
Actual values for the IEC 61850-90-5 PDU size are provided. These values allow you to know the approximate Ethernet
frame size for the data streams from each aggregator. This can help to estimate network loading. The PDU size shown in
the displays does not include the Ethernet, UDP, or IP layers. PDU sizes approaching approximately 1500 bytes result in
fragmented data frames, causing increased network traffic.
6.3.11 VOLTS PER HERTZ
PATH: ACTUAL VALUES
METERING
VOLTS PER HERTZ 1(2)
The volts per hertz actual values are displayed in this menu.
MESSAGE
PMU 1 V2:
0.0000 kV, 0.00°
MESSAGE
PMU 1 V0:
0.0000 kV, 0.00°
Range: Substituted with zero if delta-connected VTs.
MESSAGE
PMU 1 IA:
0.0000 kA, 0.00°
MESSAGE
PMU 1 IB:
0.0000 kA, 0.00°
MESSAGE
PMU 1 IC:
0.0000 kA, 0.00°
MESSAGE
PMU 1 IG:
0.0000 kA, 0.00°
MESSAGE
PMU 1 I1:
0.0000 kA, 0.00°
MESSAGE
PMU 1 I2:
0.0000 kA, 0.00°
MESSAGE
PMU 1 I0:
0.0000 kA, 0.00°
MESSAGE
PMU 1 FREQUENCY:
0.0000 Hz
MESSAGE
PMU 1 df/dt:
0.0000 Hz/s
MESSAGE
PMU 1 CONFIG CHANGE
COUNTER: 0
Range: 0 to 65535
PMU AGGREGATOR 1
PMU AGGREGATOR 1
PDU SIZE: 0
VOLTS PER HERTZ 1
VOLTS PER HERTZ 1:
0.000 pu
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...