6-24
T60 Transformer Protection System
GE Multilin
6.3 METERING
6 ACTUAL VALUES
6
6.3.8 IEC 61580 GOOSE ANALOG VALUES
PATH: ACTUAL VALUES
METERING
IEC 61850 GOOSE ANALOGS
The T60 Transformer Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. See the
Order Codes
section of chap-
ter 2 for details.
The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received
via IEC 61850 GOOSE messages sent from other devices.
6.3.9 PHASOR MEASUREMENT UNIT
PATH: ACTUAL VALUES
METERING
PHASOR MEASUREMENT UNIT
PMU 1
XFMR DIFFERENTIAL
HARMONIC CONTENT
(Xfmr Harm2 Iad, Ibd, and Icd Mag)
(Xfmr Harm5 Iad, Ibd, and Icd Mag)
BASE = 100%
XFMR RESTRAINING CURRENT
(Xfmr Iar, Ibr, and Icr Mag)
I
BASE
= maximum primary RMS value of the +IN and -IN inputs
(CT primary for source currents, and transformer reference primary current for transformer
differential currents)
Z
BASE
Z
BASE
= PhaseVTSecondary / PhaseCTSecondary, where PhaseVTSecondary and
PhaseCTSecondary are the secondary nominal voltage and the secondary nominal current of the
distance source. In case multiple CT inputs are summed as one source current and mapped as
the distance source, use the PhaseCTSecondary value from the CT with the highest primary
nominal current.
Distance source is specified in setting under
SETTINGS > GROUPED ELEMENTS > SETTING
GROUP 1(6) > DISTANCE
.
PhaseVTSecondary and PhaseCTSecondary are specified in setting under
SETTINGS > SYSTEM
SETUP > AC INPUTS
.
IEC 61850
GOOSE ANALOGS
ANALOG INPUT
1
0.000
MESSAGE
ANALOG INPUT
2
0.000
MESSAGE
ANALOG INPUT
3
0.000
↓
MESSAGE
ANALOG INPUT 32
0.000
PMU 1
PMU 1 VA:
0.0000 kV, 0.00°
Range: Va or Vab per VT bank connection
MESSAGE
PMU 1 VB:
0.0000 kV, 0.00°
Range: Va or Vab per VT bank connection
MESSAGE
PMU 1 VC:
0.0000 kV, 0.00°
Range: Va or Vab per VT bank connection
MESSAGE
PMU 1 VX:
0.0000 kV, 0.00°
MESSAGE
PMU 1 V1:
0.0000 kV, 0.00°
Table 6–2: FLEXELEMENT BASE UNITS (Sheet 2 of 2)
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...