CHAPTER 5: SETTINGS
INPUTS/OUTPUTS
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
5-247
5
I
n
is the measured overload RMS current at index n
E
n
is the accumulated energy at index n
E
n – 1
is the accumulated energy at index n – 1
The thermal overload protection element removes the
THERMAL PROT 1 OP
output operand when E < 0.05. In case of
emergency, the thermal memory and
THERMAL PROT 1 OP
output operand can be reset using
THERM PROT 1 RESET
setting.
All calculations are performed per phase. If the accumulated energy reaches value 1 in any phase, the thermal overload
protection element operates and only resets when energy is less than 0.05 in all three phases.
Table 5-34: Typical time constants
The figure shows the logic for the thermal overload protection element.
Figure 5-131: Thermal overload protection logic
5.9 Inputs/outputs
5.9.1 Contact inputs
SETTINGS
INPUTS/OUTPUTS
CONTACT INPUTS
Protected equipment
Time constant
Minimum reset time
Capacitor bank
10 minutes
30 minutes
Overhead line
10 minutes
20 minutes
Air-core reactor
40 minutes
30 minutes
Busbar
60 minutes
20 minutes
Underground cable
20 to 60 minutes
60 minutes
CONTACT INPUTS
CONTACT INPUT H5a
Summary of Contents for T35
Page 9: ...TABLE OF CONTENTS T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ix ABBREVIATIONS INDEX ...
Page 10: ...x T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 472: ...5 270 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 596: ...iv T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...