GE Multilin
T35 Transformer Protection System
5-49
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2.7 REAL TIME CLOCK
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
REAL TIME CLOCK
The relay contains a real time clock (RTC) to create timestamps for communications protocols as well as for historical data,
such as event records and oscillography. When the relay restarts, the RTC initializes from an onboard battery-backed
clock, which has the same accuracy as an electronic watch, approximately ±1 minute per month (~23 ppm). Once the RTC
is synchronized with the Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchroniz-
ing time delivered to the relay.
The
SYNCHRONIZING SOURCE
setting configures the priority sequence that the relay uses to determine which of the avail-
able external time sources synchronizes the RTC and the synchrophasor clock. A setting of None causes the RTC and the
synchrophasor clock to free-run. A setting of PP/IRIGB/PTP/SNTP, IRIGB/PP/PTP/SNTP, or PP/PTP/IRIGB/SNTP causes
the relay to track the first source named that is enabled and operational, or free-run if none of these are available. Here, PP
means a time source that is strictly compliant with PP, PTP means a time source that is not strictly compliant with PP. When
a time source fails or recovers, the relay automatically transfers synchronization as required by this setting.
See the
COMMANDS
SET DATE AND TIME
menu section of this manual to manually set the RTC.
The
REAL TIME CLOCK EVENTS
setting allows changes to the date and/or time to be captured in the event record. The event
records the RTC time before the adjustment.
To enable IRIG-B synchronization, the input
IRIG-B SIGNAL TYPE
must be set to DC Shift or Amplitude Modulated. IRIG-B
synchronization can be disabled by making this setting None.
To configure and enable PTP and/or SNTP, or to set local time parameters (for example time zone, daylight savings), use
the following sections.
b) PRECISION TIME PROTOCOL (1588)
PATH: SETTINGS
PRODUCT SETUP
REAL TIME CLOCK
PRECISION TIME PROTOCOL (1588)
REAL TIME
CLOCK
SYNCRONIZING SOURCE:
None
Range: None, PP/IRIG-B/PTP/SNTP, IRIG-B/PP/PTP/
SNTP, PP/PTP/IRIG-B/SNTP
MESSAGE
REAL TIME CLOCK
EVENTS: Disabled
Range: Enabled, Disabled
MESSAGE
IRIG-B SIGNAL TYPE:
None
Range: None, DC Shift, Amplitude Modulated
MESSAGE
PRECISION TIME
PROTOCOL (1588)
See below
MESSAGE
SNTP PROTOCOL
See below
MESSAGE
LOCAL TIME
See below
PRECISION TIME
PROTOCOL (1588)
STRICT POWER PROFILE:
Disabled
Range: Enabled, Disabled
MESSAGE
PTP DOMAIN NUMBER
0
Range: 0 to 255
MESSAGE
PTP VLAN PRIORITY
4
Range: 0 to 7
PTP VLAN ID
0
Range: 0 to 4095
MESSAGE
PTP PORT 1
Summary of Contents for T35 UR Series
Page 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Page 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...