background image

Figure 4. Accessory switch on the rear of the MicroVersaTrip Plus™ or

MicroVersaTrip PM™ Trip Unit, showing the factory settings (solid

part indicates that the switch is pushed in on that side).

Switch

Factory
Setting

Function

1

Disabled

Shunt trip activates Bell Alarm–Alarm

Only

2

Disabled

UVR trip activates Bell Alarm–Alarm

Only

3

Enabled

Protection trip activates Bell

Alarm–Alarm Only

4

Disabled

Shunt trip activates Bell Alarm with

Lockout

5

Disabled

UVR trip activates Bell Alarm with

Lockout

6

Enabled

Protection trip activates Bell Alarm

with Lockout

Table 4. Accessory switch settings, including the factory defaults.

2.

When  an  Undervoltage  Release  accessory  causes  the
breaker to trip, the contacts of the Bell  Alarm–Alarm Only
also change state. (The  factory switch setting is 

disabled

.)

3.

When 

protection 

trip 

(long-time, 

short-time,

instantaneous,  ground-fault,  or  protective-relay)  occurs,
the  contacts  of  the  Bell  Alarm–Alarm  Only  also  change
state. (The  factory switch setting is 

enabled

.)

4.

When  a  Shunt  Trip  accessory  causes  the breaker  to  trip,
the contacts  of the Bell  Alarm  with  Lockout  also  change
state. (The  factory switch setting is 

disabled

.)

5.

When  an  Undervoltage  Release  accessory  causes  the
breaker  to  trip,  the  contacts  of  the  Bell  Alarm  with
Lockout  also  change state.  (The  factory  switch  setting  is

disabled

.)

6.

When 

protection 

trip 

(long-time, 

short-time,

instantaneous,  ground-fault,  or  protective-relay)  occurs,
the contacts  of the Bell  Alarm  with  Lockout  also  change
state. (The  factory switch setting is 

enabled.

)

Procedure for Changing Switch Settings

Change  the  accessory  switch  settings  with  the  following
procedure:

WARNING:

 Before beginning this procedure, turn the breaker

off,  disconnect  it  from  all  voltage  sources,  and  discharge  the
closing springs.

AVERTISSEMENT:

  Avant  de  commencer  cette  procédure,

mettre le disjoncteur en position  OFF,  le déconnecter  de toute
tension d’alimentation, et désarmer les ressorts de fermeture.

1.

Loosen  the  four  #8-32  screws  on  the  breaker  trim-plate
assembly and remove the trim plate.

2.

Loosen the four #10-32 screws at the corner of the breaker
cover. Remove the cover from the breaker face.

3.

Pull the Trip  Unit locking lever to the right, then hold the
Trip  Unit near the battery cover  and  lift it  straight  out of
the breaker.

4.

Refer to Figure 4 and Table 4  to determine the switches  to
be changed.

5.

Push in the appropriate “Enable” or  “Disable” side  of the
switch.

6.

Confirm  all  switch  settings  before  reinstalling  the  Trip
Unit in the breaker.

7.

Pull the Trip  Unit locking lever to the right. While holding
the lever, carefully align  the connector on the rear  of  the
Trip  Unit  with  the connector in  the breaker.  Press  down
on the Trip  Unit, while holding it  near  the battery  cover.
When the Trip  Unit is fully  seated,  slide the locking lever
back to the left.

8.

Reinstall the breaker top cover and tighten the four #10-32
screws to 32 in-lb.

9.

Replace the trim plate  and  tighten the four  #8-32  screws
to 20 in-lb.

10.

Verify  that  the  switch  settings  are  correct  by  inducing
breaker  trips  from  the  Shunt  Trip  and  Undervoltage
Release (if present) and checking the responses of the Bell
Alarm–Alarm  Only  and  Bell  Alarm  with  Lockout
accessories.

Test Procedure

Test  the  Shunt  Trip  for  proper  operation  with  the  following
procedure.

1.

Turn  off the power to the Shunt  Trip.

2.

Close the breaker contacts.

3.

Apply  at  least 55%  of the rated  ac voltage  to  the  Shunt
Trip;  the breaker should trip immediately.

4.

If a Bell Alarm–Alarm Only or Bell Alarm with  Lockout  is
present, ensure  that  they activate  (or do not activate)  as
selected  by  the  MicroVersaTrip  Plus  or  MicroVersaTrip
PM Trip  Unit DIP switches.

If a Shunt  Trip  with  Lockout  has been installed, continue  with
the following steps:

5.

After  the  breaker  has  tripped  and  with  the  power  still
applied  to the Shunt  Trip  with  Lockout,  attempt  to  close
the breaker.  The  breaker  should  not close nor  attempt  to
close.

6.

If  a  MicroVersaTrip  Plus  or  MicroVersaTrip  PM  Trip
Unit is installed, check that the Trip  Unit display is active
(powered).

7.

Remove power from the Shunt  Trip  with Lockout.

8.

Attempt to close the breaker; it should close as normal.

Courtesy of NationalSwitchgear.com

Summary of Contents for SPST480

Page 1: ...480 Vac et 600 Vac doivent être utilisés avec le transformateur abaisseur detension qui est fourni The Shunt Trip or Shunt Trip with Lockout will cause the circuit breaker to trip when the control voltage is greater than 55 of the rated ac value Control power to the Shunt Trip must be removed before the breaker can be closed Control power to the Shunt Trip with Lockout must be removed for a minimu...

Page 2: ... 480 Vac and 600 Vac Shunt Trip accessories mustbeused with the supplied step down transformer AVERTISSEMENT Les modules de déclenchement shunt 480 Vac et 600 Vac doivent être utilisés avec le transformateur abaisseur detension qui est fourni Catalog Number Control Voltage Primary Connections Secondary Connections 9T58K0042 480 V H1 H4 X1 X2 9T58K0062 600 V H1 H4 X1 X3 A jumper must be placed from...

Page 3: ...ve the trim plate 2 Loosenthefour 10 32 screws at thecorner of the breaker cover Remove thecover from the breaker face 3 Pull the Trip Unit locking lever to the right then hold the Trip Unit near the battery cover and lift it straight out of thebreaker 4 Refer to Figure 4 and Table 4 to determine the switches to bechanged 5 Push in the appropriate Enable or Disable side of the switch 6 Confirm all...

Page 4: ...ck that the Shunt Trip with Lockout control power is applied at greater than 55 of the rated ac voltage Check that the accessory is completely inserted re insert if necessary Note that an otherwise unpowered Trip Unit is powered by an energized Shunt Trip accessory Check that the Shunt Trip with Lockout accessory is completely inserted 4 The breaker will not close manually when the Shunt Trip or S...

Reviews: